table 7-7 Parameters of each equipment tab
Data
Type
DataID
State
Invert
Coefficie-
nt
Uint
Data
Name
YC
1
Y
N
1000
W
P
YC
2
Y
N
1000
Var
Q
YX
3
Y
Y
1
NA
On-grid
YX
4
Y
N
1
NA
Off-grid
YM
5
Y
N
1
kWh
E-Daily
YK
6
Y
N
1
NA
Power On
/ Off
YT
7
Y
N
1
kW
P-Set
YT
8
Y
N
1
Var
Q-Set
table 7-8 Description of parameter
Parameter
Value
Description
Data Type
-
Data type
Data ID
-
Data type
State*
Y
Data is uploaded to the background via the
IEC104 communication protocol
N
Data is not uploaded to the background
Invert*
Y
Negate, 0 is 1, and 1 is 0, available for
telesignalling only
N
No negate, 0 is 0 and 1 is 1
Coefficient*
-
Coefficient, available for telemetry, remote
pulse, and remote regulating only
Uint
-
Unit, available for telemetry, remote pulse, and
remote regulating only
NA indicates no unit
Data Name
-
Data name in multiple languages
Note: * indicates that the parameters should be set according to onsite conditions.
step 5 Open the sheet
Device List
of the IEC104 forwarding point table to sort the devices.