75
8.3.2.5 Digital Input
When using the digital signal at the DI port of the Logger1000 as the dispatching input, set
the
Reactive Control Mode
to
Digital input
.
step 1 Click
Power control→Reactive power
to enter the reactive power interface.
step 2 Set the
Reactive Control Mode
to
Digital input
.
step 3 Set DI control parameters. For specific parameter description, refer to the following table.
table 8-10 Parameter description
Parameter
Description
Communication
abnormality output (%)
Communication is abnormal, and specified dispatch output
value is delivered.
Control method
Open-loop control
: Reactive instruction controlled by DI is
sent to power output port of the inverter, thereby achieving
active power control.
Closed-loop control
: Reactive instruction controlled by DI
is used as target value and reactive power and power factor
of the meter need to be collected and used as input
parameters, and reactive power compensation ratio is
calculated and sent to power output port of the inverter.
Generally, this strategy is used for improving the power
factor of the property boundary point.
Select energy meter*
Select Smart Energy Meter involved in power regulation
Control cycle
Time interval of delivering dispatching instructions
Parameter range: 5~60s
Q-Method
PF
: set the power factor as the target value
%
: set reactive power percentage
Note: *Only when the
Control method
is set to
Closed-loop control
, the parameter
Select
energy meter
is settable.
The open-loop control has the
PF
Q-Method, and the closed-loop control has the
PF
Q-Method only when the meter is selected.
step 4 Add digital input manner
Select the desired DI channel, fill in the
Percentage (PF)
, and click
Save
.
- - End
Subsequent Operation
Delete digital input manner: select a digital input manner that needs to be deleted, and click
Clear data
.
User Manual