background image

8

Indicator

Indicator

(print)

LED color

LED status

Description

Running

indicator (RUN)

Red/green

Off

No external power supply

connected

Slow flash (Green)

Normal running

Slow flash (Red)

Device alarm

Steady on (Red)

Logger1000 running fault

4G indicator

(4G) *

Blue

Off

No data communication

Steady on

4G connected successfully

Slow flash

Data communication in

process

WLAN indicator

(WLAN)

Blue

Off

No data communication

Steady on

WLAN connected

successfully

Slow flash

Data communication in

process

Note: * Only the Logger1000A is equipped with the 4G indicator.

Slow flash means that the indicator flashes once every second.

Slow flash of the communication indicator indicates data communication in process. If
there has been no data communication with iSolarCloud for 10s, the indicator will keep
steady on.

Dimensions

figure 2-2

Dimensions

Width (W)

Height (H)

Depth (D)

200mm

110mm

60mm

2 Product Description

User Manual

Содержание Logger1000

Страница 1: ...Logger1000A Logger1000BData LoggerUser ManualLogger1000A_B UEN Ver19 202211 M H 001405 User Manual Data Logger Logger1000A Logger1000B Logger1000A_B UEN Ver19 202211...

Страница 2: ......

Страница 3: ...anual are owned by SUNGROW All other trademarks or registered trademarks mentioned in this manual are owned by their respective owners Software Licenses It is prohibited to use data contained in firmw...

Страница 4: ...t the following requirements Know electronic electrical wiring and mechanical expertise and be familiar with electrical and mechanical schematics Have received professional training related to the ins...

Страница 5: ...l Indicates high risk potential hazards that if not avoided may lead to death or serious injury Indicates moderate risk potential hazards that if not avoided may lead to death or serious injury Indica...

Страница 6: ......

Страница 7: ...ng Application 5 2 4 Product Introduction 7 3 Unpacking and Storage 9 3 1 Scope of Delivery 9 3 2 Identifying the Logger1000 10 3 3 Checking upon Receiving 10 3 4 Storage 10 4 Mechanical Mounting 12 4...

Страница 8: ...erface 33 7 1 Running Requirements 33 7 2 Login Steps 33 7 2 1 WLAN Login 33 7 2 2 Ethernet Login 34 7 3 Web Main Interface 34 7 4 Web Menu 35 7 5 Operation Procedure 36 7 6 Overview 37 7 6 1 General...

Страница 9: ...8 Grid Dispatching Function 60 8 1 Function Description 60 8 2 Interface Description 61 8 2 1 Digital Control Interface 61 8 2 2 Analog Control Interface 62 8 2 3 DRM Control Interface 63 8 3 Power Co...

Страница 10: ......

Страница 11: ...hibited under any circumstances Tighten the screws with the specified torque using tools when fastening the product and terminals Otherwise the product may be damaged And the damage caused is not cove...

Страница 12: ...ime 1 2 Installation Safety Make sure there is no electrical connection before installation Make sure to avoid the water and electricity wiring in the wall before drilling Improper installation may ca...

Страница 13: ...ll cables used shall comply with the requirements of local laws and regulations and must be firmly attached properly insulated and adequately dimensioned Comply with the regulations related to the loc...

Страница 14: ...intenance operations beyond this manual If necessary contact SUNGROW for maintenance Otherwise the losses caused are not covered by the warranty If a fault occurs only restart the device after the fau...

Страница 15: ...ta collection from various environment sensors Smart Energy Meters Meteo Stations inverters and other equipment Auxiliary maintenance Support of batch inverter parameter setting and software upgrading...

Страница 16: ...6 The Logger1000 can be connected to iSolarCloud via the router or connected to the iSolarCloud via the WLAN or 4G network 2 Product Description User Manual...

Страница 17: ...ownstream devices The Logger1000 is equipped with grid dispatching function including active power control reactive power regulation etc 2 4 Product Introduction Appearance figure 2 1 Appearance Item...

Страница 18: ...rocess WLAN indicator WLAN Blue Off No data communication Steady on WLAN connected successfully Slow flash Data communication in process Note Only the Logger1000A is equipped with the 4G indicator Slo...

Страница 19: ...resistor in parallel on the A and B lines at the head or tail end of the bus D Nylon cable tie Used to tie cables E Fastener assembly 4 sets M4X16 used for wall mounting to fasten the device on the m...

Страница 20: ...ng to 3 1 Scope of Delivery Ensure that the device type is correct Check the device thoroughly and ensure there are no visible damages If there are any problems contact SUNGROW or the forwarding compa...

Страница 21: ...k the packing case for intactness and replace it immediately when necessary Unpack and check the Logger1000 in powered on state if it has been stored more than half a year The Logger1000 must be packe...

Страница 22: ...an be installed only indoors Ambient temperature range 30 to 60 The relative humidity should not exceed 95 If otherwise the internal components will be damaged Take anti moisture and anti corrosion me...

Страница 23: ...de rail mounting manner and users can select either one according to onsite condition 4 3 1 Wall Mounted Installation Mount the Logger1000 onto the concrete wall or metal surface according to onsite c...

Страница 24: ...ing process to avoid dust inhalation or contact with eyes step 4 Secure the expansion bolts into the holes with a rubber mallet If the Logger1000 is installed onto the metal surface skip performing th...

Страница 25: ...via the rail buckles as shown in the figure below on the back of it step 1 Install and secure the guide rail at the appropriate location step 2 Slight press down the recessed part under the buckle of...

Страница 26: ...that the Logger1000 is firmly installed End 4 4 Installing Antenna The sucker antenna base should be placed on a metal surface outside the container to avoid impact on signal reception Antenna entry...

Страница 27: ...stall and secure the power box guide rail at the appropriate location The power box should be 200mm away from the Logger1000 to ensure that the power cable from the power box can be connected to the p...

Страница 28: ...18 step 3 The installation of the power box and Logger1000 is completed End 4 Mechanical Mounting User Manual...

Страница 29: ...d at the bottom of Logger1000 and the wiring area is shown in the figure below figure 5 1 Wiring area table 5 1 Port description Port Function Description 24V OUT 24V power output 24V 5 the max output...

Страница 30: ...rts the communication distance should not exceed 1 000m 5 3 Connection to PV Devices Devices in the PV system that can be connected to the Logger1000 include the inverter Meteo Station Smart Energy Me...

Страница 31: ...85 communication cable must be the shielded twisted pair with the shielding layer single point grounded When a multi core multi strand copper wire cable is used crimp an appropriate euro style termina...

Страница 32: ...ponding RS485A B signal cables out Insert cord end terminals into signal cable RS485 A and signal cable RS485 B and crimp them with a crimper Cut off the redundant signal cable and warp it with a heat...

Страница 33: ...ports of Logger1000 it is recommended to connect different types of devices to different RS485 ports separately The addresses of devices on each RS485 bus must be different from one another and within...

Страница 34: ...tion RS485 Connection The following figure shows the connection between the Logger1000 and the Smart Energy Meter Connect the communication cable led from the Smart Energy Meter to the RS485 port of t...

Страница 35: ...tegory is recommended 5 3 4 Connection to Meteo Station Meteo Station includes standard Meteo Station and discrete Meteo Station The discrete Meteo Station consists of several sensors It is recommende...

Страница 36: ...backgrounds and communicate by using the standard protocol The following figure shows the connection between the Logger1000 and the background The Logger1000 can be connected to multiple monitoring b...

Страница 37: ...orts DC24V power supply Prepare two core DC cable three core AC cable and grounding cable before wiring Power cable specifications are shown in the table below table 5 2 Power cable specification Cabl...

Страница 38: ...ect the DC cable led from the 24V OUT port of the Logger1000 to other devices that need 24V DC power supply step 3 Connect the stripped grounding cable to the corresponding port of the Logger1000 step...

Страница 39: ...g distance parallel cable routing of power cables and other cables thereby reducing electromagnetic interference due to output voltage transient The distance between the power cable and communication...

Страница 40: ...tors of Logger1000 normally flash 4 Connect the debugging PC to the ETH port of the Logger1000 via the network cable default IP address of ETH 12 12 12 12 Log in the Web at 12 12 12 12 through the IE...

Страница 41: ...ation is China Station Users in mainland China access the China Station users in Europe access the Europe Station users in Australia access the Australian Server and users in other regions access the...

Страница 42: ...the QR code on the front label of the Logger1000 or manually input the S N to add communication equipment For details refer to the Quick Guidance of iSolarCloud App Scan the bottom QR Code to view or...

Страница 43: ...N Login step 1 Open the wireless network settings of the PC search for the wireless network SG A1234567890 of the Logger1000 and connect the PC to the wireless network of the Logger1000 without passwo...

Страница 44: ...r1000 is the same as that of the Logger1000 The IP address is 12 12 12 X For example the IP address of the PC can be set to 12 12 12 125 and the subnet mask is 255 255 255 0 IP of Logger1000 is 12 12...

Страница 45: ...terface D Help Display the basic configuration steps of the Logger1000 E Language menu Click the button to select the desired language F User Display the current login user G Information icon WLAN con...

Страница 46: ...communicate with upstream devices Refer to the chapter 7 10 10 Port Parameter step 3 Calibrate the system time Check whether the current system time is correct and perform manual time synchronization...

Страница 47: ...rameters Refer to the chapter 7 10 10 Port Parameter Transfer configuration transfer the data connected by the system to the background Refer to the chapter 7 10 6 iSolarCloud 7 10 9 Third party porta...

Страница 48: ...7 3 Initial Parameter Click Device monitoring Initial Parameter to enter the corresponding interface and set initial parameters Select the meter set PT Transformation Ratio CT Transformation Ratio Met...

Страница 49: ...value of the device step 3 Select Settings set Register Address Data Type and set Value and click the button Save Parameters can be set for a single device For parameters that need to be set refer to...

Страница 50: ...can be automatically searched and added 7 8 1 1 Auto search The Auto Search function is used for SUNGROW string inverter to which addresses will be automatically allocated step 1 Click Device Device...

Страница 51: ...pop up window and fill in the information required End 7 8 1 5 Add the Third party Meter Import Files step 1 Click Device Device List to enter the corresponding interface step 2 Click Add Device selec...

Страница 52: ...number of the meter Debug Address The device address to be read when click Read Back the range is Beginning Address Beginning Address Quantity of Device 1 Modbus Address Refer to the communication pr...

Страница 53: ...setting End 7 8 1 7 Add the Third party Meteo staion Import Files step 1 Click Device Device List to enter the corresponding interface step 2 Click Add Device select Meteo Staion option in the Device...

Страница 54: ...select up to 13 objects for setting For the corresponding parameters such as register address register type etc please refer to the user manual of the connected meteo station step 6 Select the points...

Страница 55: ...dential inverter and string inverter step 1 Click Device Firmware Update to enter the corresponding interface step 2 Click the button Select a Firmware File Select an upgrading file and import it to t...

Страница 56: ...o enter the corresponding interface On this interface users can view history information 7 10 System 7 10 1 Running Information Click System Run Information to enter the corresponding interface Inform...

Страница 57: ...will pop up and click Confirm to continue the reset all settings operation End Restoring the factory settings refers to restoring all modified settings to the factory state and will not clear the data...

Страница 58: ...he access link in the URL field to enter the Remote Maintenance interface Enter the device S N and password and click Login to perform remote maintenance End 7 10 4 Message Export step 1 Click System...

Страница 59: ...list and select the local time zone Enter the Date and Time and click Save to manually set the time of the Logger1000 When the clock source is set to NTP time of all devices can be synchronized Click...

Страница 60: ...nation address Destination port Chinese Server iot isolarcloud com TCP 19999 TCP 16668 TCP 8443 TCP 80 TCP 443 UDP 123 European Server iot isolarcloud eu Australian Server auiot isolarcloud com Intern...

Страница 61: ...uration Tools to export the IEC104 forwarding point table step 2 Open the sheet Introduce of the IEC104 forwarding point table where data of five types telemetry telesignalling remote pulse remote con...

Страница 62: ...background via the IEC104 communication protocol N Data is not uploaded to the background Invert Y Negate 0 is 1 and 1 is 0 available for telesignalling only N No negate 0 is 0 and 1 is 1 Coefficient...

Страница 63: ...Reserved YX Addr Reserved telesignalling address Reserved YC Addr Reserved telemetry address Reserved YM Addr Reserved remote pulse address Reserved YK Addr Reserved remote control address Reserved YT...

Страница 64: ...tep 1 Click System Transfer Configuration MODBUS to enter the corresponding interface step 2 For the white list setting refer to 7 10 7 1 White list setting End 7 10 8 2 Client Mode In the Client Mode...

Страница 65: ...ck Save Set the FTP path and name it as FTP server directory For example for the name SUNGROW is the root directory and SUNGROW is the directory where data is stored on the FTP server End 7 10 10 Port...

Страница 66: ...slave nodes can be configured simultaneously if the networking between master and slave nodes is finished Click Select Measuring Point s to enter the Frequency interface check the frequency point of...

Страница 67: ...set All Settings EyeW485 H only Restore factory settings of the master node of EyeW485 Rebooting EyeW485 H EyeW485 Reboot the master and slave nodes of EyeW485 7 10 10 3 Ethernet Perform Ethernet sett...

Страница 68: ...e PC or mobile phone can be connected to the Logger1000 via the WLAN function Click System Port Parameter WiFi to enter the corresponding interface Click Hotspot to enter the corresponding interface t...

Страница 69: ...ding ID Select the winding ID Check whether the Array ID and Winding ID are correct If not the device may go offline step 2 Click Next to set the slave node Select the device to be set and click Synch...

Страница 70: ...nly includes active power control and reactive power regulation The Logger1000 can control device power output according to the local preset instructions In addition it can receive regulation instruct...

Страница 71: ...Logger1000 and a sum of 5 digital input ports are provided as shown in the figure below table 8 1 Digital control interface signal definition Signal Definition DI Enabling switch for converting AI fu...

Страница 72: ...grid dispatching signal in the dry contact communication manner Wiring of the active power dry contact is shown in the figure below Wiring of the reactive power dry contact is shown in the figure bel...

Страница 73: ...function Wiring between the Logger1000 and the DRED is as follows The DRM interface requires that the Logger1000can be connected to the DRED via the corresponding wiring terminal or RJ45 connector 8...

Страница 74: ...mote monitoring background is connected active instruction of remote dispatching is used as target value and active power compensation ratio is calculated and sent to the power output port of the inve...

Страница 75: ...t energy meter transformer is settable step 4 After finishing parameter setting click Save to save the operation End 8 3 1 3 Local Power Control If active dispatching instruction or dispatching target...

Страница 76: ...nd used as input parameter and active power compensation ratio is calculated and sent to the power output port of the inverter Generally this strategy is used for anti backflow or avoiding zero power...

Страница 77: ...ed loop control the parameter Select energy meter is settable step 4 Add local power control manner Fill in Start time and Percentage Fixed Value of Active Power and click Save End Subsequent Operatio...

Страница 78: ...ter needs to be collected and used as input parameter and active power compensation ratio is calculated and sent to the power output port of the inverter Generally this strategy is used for anti backf...

Страница 79: ...compensation ratio is calculated and sent to the power output port of the inverter Generally this strategy is used for fast and accurate active power regulation In case a Smart Energy Meter is select...

Страница 80: ...3 Select a country and PPC type and click Save End 8 3 1 8 Scheduling Prohibited Set the active control mode to Scheduling prohibited if the Logger1000 is prohibited to perform active dispatching on...

Страница 81: ...ower control Closed loop control Remote monitoring background is connected and reactive instruction of remote dispatching is used as target value reactive power and power factor of the meter need to b...

Страница 82: ...to enter the reactive power interface step 2 Set the Reactive Control Modeto Local Power Control step 3 Set local dispatching parameters For specific parameter description refer to the following table...

Страница 83: ...e parameter Select energy meter is settable When selecting an energy meter the Logger used must be the one manufactured by SUNGROW step 4 Add local power control manner Fill in Start time and Percenta...

Страница 84: ...e interval of delivering dispatching instructions Parameter range 5 60s AI port AI1 AI4 available Q Method PF set the power factor as the target value set reactive power percentage Min Max When Q Meth...

Страница 85: ...wer factor of the meter need to be collected and used as input parameters and reactive power compensation ratio is calculated and sent to power output port of the inverter Generally this strategy is u...

Страница 86: ...on the inverter step 1 Click Power control Reactive power to enter the reactive power interface step 2 Set the Reactive Control Mode to Scheduling prohibited and click Save End 8 3 3 Emergency Button...

Страница 87: ...t leave any screws washers or other metallic parts inside the Logger1000 to avoid damages to the Logger1000 Wait at least 5 minutes after the Logger1000 stops and then perform operations on it Five Sa...

Страница 88: ...Terminal and cable connection Check if the screws of the control terminals are loose Refasten them with screwdriver if necessary Check if the connection copper bar or screws are discoloring Visually...

Страница 89: ...incorrectly 3 The devices that do not support automatic search are not manually added such as Meteo Station and Smart Energy Meter 4 The address of the manually added device is inconsistent with the a...

Страница 90: ...evice connection is correct 3 Check if there is a device replaced If so research or add the device manually If the device is removed conduct the Device List operation through the Delete Cannot communi...

Страница 91: ...B39 B40 B41 TD SCDMA B34 B39 CDMA BC0 GSM 900 1800 MHz WCDMA B1 B8 WLAN communication 802 11 b g n ac HT20 40 80MHz 2 4GHz 5GHz Power Supply DC input 24VDC max current 1 2A DC output 24VDC 0 5A Power...

Страница 92: ...e greater than 1000V 10 3 Quality Assurance When product faults occur during the warranty period SUNGROW will provide free service or replace the product with a new one Evidence During the warranty pe...

Страница 93: ...caused by unexpected natural factors For faulty products in any of above cases if the customer requests maintenance paid maintenance service may be provided based on the judgment of SUNGROW 10 4 Cont...

Страница 94: ...M H 001405 www sungrowpower com Sungrow Power Supply Co Ltd...

Отзывы: