69
8.3.1.5 Digital Input
When using the digital signal at the DI port of the Logger1000 as the dispatching input, set
the active control mode to
Digital input
.
step 1 Click
Power control→Active power
to enter the active power interface.
step 2 Set the active control mode to
Digital input
.
step 3 Set DI control parameters. For specific parameter description, refer to the following table.
table 8-6 Parameter description
Parameter
Description
Communication abnormality
output (%)
Communication is abnormal, and specified dispatch output
value is delivered.
Control method
Open-loop control
: Active instruction controlled by DI is
sent to the power output port of the inverter, thereby
achieving active power control.
Closed-loop control
:
•
In case no Smart Energy Meter is selected, active
instruction controlled by DI is used as target value, and
active power compensation ratio is calculated and sent
to the power output port of the inverter. Generally, this
strategy is used for fast and accurate active power
regulation.
•
In case a Smart Energy Meter is selected, active
instruction controlled by DI is used as target value,
active power of the meter needs to be collected and
used
as
input
parameter,
and
active
power
compensation ratio is calculated and sent to the power
output port of the inverter. Generally, this strategy is
used for anti-backflow or avoiding zero power feed-in.
Select energy meter*
Unselected
Select Smart Energy Meter involved in power regulation
Control cycle
Time interval of delivering dispatching instructions
Parameter range: 5~60s
Q-Method
kW
: set active power value.
%
: set active power percentage.
Note: *Only when the control method is set to
Closed-loop control
, the parameter
Select
energy meter
is settable.
step 4 Add digital input manner.
Select the desired DI channel, fill in the
Percentage (Fixed Value of Active Power)
, and
click
Save
.
- - End
User Manual
Содержание Logger1000
Страница 2: ......
Страница 6: ......
Страница 10: ......
Страница 28: ...18 step 3 The installation of the power box and Logger1000 is completed End 4 Mechanical Mounting User Manual...