Page 16
980™ Series
7.0 Power Requirements
Sundance Spas hot tubs are designed to provide optimum
performance and flexibility of use when connected to their
maximum electrical service. However, they are shipped
factory configured for their most common preferred
electrical connection.
If you prefer, a qualified technician can perform a minor circuit board
modification that allows the hot tub to operate on a different electrical
service (see table below).
7.1
North American 60 Hz Power Options
North American 60 Hz
Voltage
240 VAC
240 VAC
240 VAC
Max. Current Draw:
28A
39A
48A
Frequency:
60 Hz
60 Hz
60 Hz
Number of Wires:
3
3
3
Circuit Breaker (2-Pole):
40A*
50A**
60A***
* In the 40A configuration, the heater
will not operate
while any jets
pump is running.
** In the 50A configuration, the heater
will operate
when one jets pump is
running, but
will not operate
while two jets pumps are running.
This is
the factory default setting.
*** In the 60A configuration, the heater
will operate
while two jets pumps
are running.