2-4
Sun Netra X4450 Server Service Manual • August 2008
5. Shut down the server.
You can shut down the server from the CLI, or you can use the Power button on
the front of the server to initiate a graceful system shutdown. This button is
recessed to prevent accidental server power-off. Use the tip of a pen to operate
this button.
▼
Disconnect the Cables From the Server
Caution –
The system supplies standby power to the circuit boards even when the
system is powered off.
1. Label all of the cables connected to the server.
2. Disconnect the following cables as appropriate:
■
PCI cards
■
Alarm
■
TTYA
■
SER MGT
■
NET MGT
■
USB ports
■
Network ports
■
Power supplies
▼
Remove the Server From the Rack
Remove the server from the rack prior to performing cold-swappable replacement
procedures.
Caution –
The server weighs approximately 64 lbs (32 kg). Two people are required
to dismount and carry the chassis.
1. Remove the server from the rack.
The steps to remove the server from the rack depend on the mounting kit. For
sliding mounting kits, you can simply release the slides to remove the server. For
hardmount kits, you must remove the securing screws from the front and rear
brackets.