Other Settings 

○Reset operation 

The Accumulated Flow, Peak Value, and Bottom Value can be reset. 

To reset the accumulated value, press the DOWN and SET buttons simultaneously for 1 second or longer. 

Resetting the accumulated flow is possible only when the accumulated flow is displayed. 

Resetting the peak value and bottom value is effective for the measurement target displayed in the peak 

display or bottom display. 

 

 

○Display select function 

The number of accumulated flow rate display digits can be temporarily switched when the temperature and 

accumulated flow rate are set in the measurement display settings. 

The normal accumulated display consists of the mantissa part (maximum 6 digits) and [Power value 

display] indicated by the index part displayed by x10

6

 or x10

3

If the DOWN button is pressed for 1 second, the mantissa part will be displayed in 9 digits and the power 

value will be displayed as x10

3

 

 

 

: If there is no button operation for 30 seconds while the 9-digit power is displayed, the number of displayed powers will return to 

6 digits. 

: When the temperature is set to "hide", the displayed power value is fixed at 9 digits. 

 

 

○Zero-clear function 

When the pressure is displayed in the measurement display setting, the displayed value can be adjusted to 

zero within the range of ±7%F.S. from the factory default value. 

(The zero clear range varies by ±1% F.S. due to variation between individual products. 

When the UP and DOWN buttons are pressed simultaneously for 1 second or longer in measurement 

mode, the image below is displayed and the displayed value is reset to zero. 

The display returns to measurement mode automatically. 

 

 

 

 

Содержание AMS20

Страница 1: ...No PF OMA1007 PRODUCT NAME Air Management System MODEL Series Product Number AMS20 AMS30 AMS40 AMS60...

Страница 2: ...y 67 Function selection mode 67 Default setting 68 F0 Reference condition Units selection function 69 F3 Select digital filter 71 F6 Fine adjustment of display value 72 F13 Setting for reverse display...

Страница 3: ...2 No PF OMA1007 Other Settings 93 Maintenance 96 Forgotten the Security Code 96 Troubleshooting 97 Error display 100 Specifications 103 Characteristics data 107 Dimensions 114 Accessories 126...

Страница 4: ...to any possibility of equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe i...

Страница 5: ...he failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are exclu...

Страница 6: ...ult Check the specifications before use Do not use in an environment where flammable explosive or corrosive gases are present Otherwise fire explosion or corrosion may occur The product is not designe...

Страница 7: ...g voltage of the load before use Do not apply a load that exceeds the max load voltage or current This may cause damage or shorten the lifetime of the product Data stored by the product is not deleted...

Страница 8: ...acer with bracket Y200T 2 D Y300T 2 D Y400T 1 D Y600T 2 D Part No of spacer Y200 D Y300 D Y400 D Y600 D Tightening torque 0 36 0 036 1 2 0 05 1 2 0 05 2 0 0 1 When the air combination is fixed on a wa...

Страница 9: ...not mount the body with the bottom facing upwards Do not mount the product with the display facing upward Retention of air can cause an inability to measure accurately Do not insert metal wires or oth...

Страница 10: ...th a new one Wire correctly Incorrect wiring may cause malfunction or damage to the product Do not perform wiring while the power is on Otherwise damage to the internal components may result causing m...

Страница 11: ...product with built in surge protection The product is CE UKCA marked but not immune to lightning strikes Take measures against lightning strikes in the system Mount the product in a location that is...

Страница 12: ...tput according to the condition before setting Check the effect on the equipment before setting Stop the control system for setting if necessary Do not touch the LCD during operation The display can v...

Страница 13: ...12 No PF OMA1007 Model Indication and How to Order Air Management System Standby E P regulator type...

Страница 14: ...13 No PF OMA1007 Air Management System Standby regulator type...

Страница 15: ...body size 30 E400 D 1 For body size 40 E600 D 1 For body size 60 Wireless adaptor EXW1 A11N X1 For wireless system M12 connector cable 320 mm 2 EXA1 AC1 For wiring Hub to each device M12 connector ca...

Страница 16: ...agement Hub Manage overall Air Management System devices communication to upper layer and digital input module for signal from external devices 3 Residual Pressure Relief Valve According to orders fro...

Страница 17: ...gnal from external devices 3 Residual Pressure Relief Valve According to orders from the Air Management Hub stop providing pressure and exhaust outlet pressure Soft start feature a module for the valv...

Страница 18: ...ve for identification marker such as input output signal name or unit address 9 Connector Power Connector for power supply 10 FE terminal Terminal to connect FE to Ground 11 Wireless adaptor connector...

Страница 19: ...nd the display shown on the Sub display or increases the set point SET button Press this button to change the mode and to set a value DOWN button Selects the mode and the display shown on the Sub disp...

Страница 20: ...the measured flow rate exceeds standby flow rate threshold to the set duration When the AMS returns to Operation mode AMS shall be back to Standby mode without waiting for Standby ON Delay time DHCP A...

Страница 21: ...effective in avoiding the effects of pulsation I Idle Base has received the FAIL SAFE command and remains idle The output state can be set to CLEAR HOLD or Software Control using the parameter settin...

Страница 22: ...to the power supply line Pressure characteristics Indicates the change in the display value when the fluid pressure changes Pressure ramp up duration Sets time to reach the setting pressure from isol...

Страница 23: ...display value caused by ambient temperature changes U Units selection function A function to select display units other than the international unit SI unit specified in the new Japanese measurement l...

Страница 24: ...eads and sealant do not get inside the piping Fit the raised part of the spacer to the recessed part groove for the raised part of the product Tighten the retainer A with two hexagon socket head cap s...

Страница 25: ...the power supply Connector Pin No Signal Details 1 DC 24 VDC 2 NC Not connected 3 DC 0 V 4 NC Not connected 2 Communication line M12 4 pin D coded Socket Use this port for Industrial Ethernet communic...

Страница 26: ...port Port Function 1 Connection to Residual Pressure Relief Valve 2 Connection to standby regulator 3 Digital input signals for standby and isolation 4 User configurable port IO Link or DIO AMS A Seri...

Страница 27: ...t connected 3 0 V 0 V 4 C Q IO Link 5 NC Not connected Standby regulator ARS side M12 3 pin A coded Socket Connector Pin No Signal Details 3 0 V 0 V 4 C Q Output 5 NC Not connected Digital input signa...

Страница 28: ...I Q Digital Input 3 0 V 0V 4 C Q IO Link Digital Input PNP Digital Output PNP 1 5 NC Not Connected 1 Can be changed by setting parameters Connection to Wireless adaptor Connect wireless adaptor if wir...

Страница 29: ...BF NS OFF PROFINET communication established Green ON OPC mode operating EtherNet IPTM communication is established Green flashing EtherNet IPTM communication is not established Red flashing Paring mo...

Страница 30: ...ation L A PORT1 OFF PORT1 No Link No Activity Green ON PORT1 No Link No Activity Green Flashing PORT1 No Link No Activity L A PORT2 OFF PORT2 No Link No Activity Green ON PORT2 No Link No Activity Gre...

Страница 31: ...adaptor SA OFF Standalone mode Green ON Wireless mode Red flashing Pairing mode synchronized with ST PWR OFF Power not supplied Green flashing Power supply voltage is abnormal Green ON Power supply vo...

Страница 32: ...Hz IO Link device not connected Green flashing 2 Hz Connected device matching error Device process data mapping error Data storage writing error Green ON IO Link device in communication Red ON Short c...

Страница 33: ...ping error Green ON IO Link device communicating Red ON Short circuit detected 24 V of C Q DI Digital Input OFF Input signal OFF Orange ON Input signal ON Red ON Short circuit detected 24 V DO Digital...

Страница 34: ...ON Unrecoverable error is detected OFF US1 for control power supply is OFF W SS Green ON The level of received radio wave power is 3 Green flashing 1 Hz The level of received radio wave power is 2 Gre...

Страница 35: ...ion Power LED Green ON Normal operation Green flashing Communication system error OFF Internal memory error No power supplied Communication LED Green ON IO Link communication not established Green fla...

Страница 36: ...AC D F R L system and can be combined with existing installations Two versions of the Air Management Hub are available base type and remote type These can be combined to create a wireless network of u...

Страница 37: ...comes with no data communication It could be used as standalone Optionally a wireless adapter can be connected to use the Air Management Hub as a wireless remote 3 Standby regulator manual pressure se...

Страница 38: ...cal pressure setting type uses an ITV module to set the operation pressure and standby pressure 5 Residual Pressure Relief Valve VP A VP valve module can be used for isolation mode with an optional so...

Страница 39: ...ement Hub has one spare port which can be configured to be either 1 DI IO Link 1 DI 1 DO 2 DI Additional compact wireless remotes EXW1 RD can be paired to an AMS wireless base to provide extra digital...

Страница 40: ...39 No PF OMA1007...

Страница 41: ...immediately return to Standby Mode If at any point the 8 Isolation input signal is OFF 0 V Low the AMS will be forced into isolation mode Hysteresis can also be set for the standby flow rate threshol...

Страница 42: ...lowing figure shows an example timing diagram for the NC type AMS A and NO type AMS B This timing chart is for reference only the actual be haviour depends on the machine volume connected to the AMS o...

Страница 43: ...crewdriver Refer to the flowing table to set the DIP switches AMS Switch Position Switch Number 1 2 3 4 Communication Method Regulation Type NO NC Wireless Pairing Mode Base type OFF Industrial Ethern...

Страница 44: ...vailable Available Mask AMS Standalone Remote type Machine to AMS control Monitor Data Via Digital Input Via AMS Base Via AMS Base Switch No 1 Position Communication method Standby and Isolation contr...

Страница 45: ...the web server connect a PC to the network and enter the Air Management Hub IP address into a web browser Ensure that the Air Management Hub and PC are on the same IP subnet The default login credenti...

Страница 46: ...e set to pairing mode Starting with DIP switch 4 of SW 1 in the OFF position perform the sequence ON OFF ON The SF MS ST and BF NS SA LEDs of each device will flash red Connect to the webserver The av...

Страница 47: ...Air Management Hub display and buttons or via the webserver Refer to F41 Force AMS Mode setting to set parameter via buttons page 82 The following example shows the parameter set via the Web server Na...

Страница 48: ...g For the ARS type AMS the operation pressure is the same as the AMS supply pressure To set the standby pressure the AMS must first be forced into standby mode When in standby mode set the standby pre...

Страница 49: ...TV type AMS the operation pressure and standby pressure are set using the webserver ITV buttons or via Fieldbus Setting via Webserver To change the operating pressure Standby Pressure or pressure ramp...

Страница 50: ...tton again to allow editing and use the arrows to modify the value Press the S button to set the value Measurement mode Press the SET button Pressure set point in operation mode Press the UP or DOWN b...

Страница 51: ...he screen is seconds x10 Once the correct value has been selected press the S button to set it Measurement mode Press the SET button for 2 seconds Menu display Press the UP button 4 times Menu display...

Страница 52: ...n be set by Webserver display buttons on the Air Management Hub or via Industrial Ethernet Refer to F40 Standby function setting to set parameter using the buttons page 79 Setting via Webserver Naviga...

Страница 53: ...nagement Hub Base to change this setting The Air Management Hub Remote parameter Module parameter overwrite controls the priority for the parameter setting If enabled the parameters set using the butt...

Страница 54: ...emsPerCall 100 MaxNodesPerBrowse 20 MaxNodesPerMethodCall 5 MaxNodesPerNodeManagement 0 MaxNodesPerRead 100 MaxNodesPerRegisterNodes 1 MaxNodesPerTranslateBrowsePathsToNodeIds 20 MaxNodesPerWrite 30 M...

Страница 55: ...an be enabled or disabled for each OPC UA node Historical Data Buffer Sampling Cycle Sampling cycle time for the buffer The parameter is applicable for all nodes which enabled the data buffer Number o...

Страница 56: ...ow the process data is mapped for big and little endian Comparison of big endian and little endian UaExpert Connection The example below uses the OPC UA client UaExpert to connect the wireless base OP...

Страница 57: ...56 No PF OMA1007 Expand the AMS server and select the None security option OPC UA security type Click the Connect button and enter the username and password for the AMS both are admin OPC UA login...

Страница 58: ...57 No PF OMA1007 Navigate in the Address Space to the ParameterSet and expand it to see all the configured nodes available on the AMS Server address base...

Страница 59: ...ase type then add any additional remote units This example shows a system with full diagnostics one AMS Base and two AMS remotes Each AMS component can be configured in Device Overview Select the comp...

Страница 60: ...formation 1 7 Remote diagnostic information 2 8 Remote registration information 1 9 Remote registration information 2 10 Accumulated flow high word Unit 10 L or ft3 11 12 Accumulated flow low word 13...

Страница 61: ...Force isolation mode from PLC OPC UA Digital Input 22 ITV control pressure measurement value high byte Unit kPa 23 ITV control pressure measurement value low byte 24 ITV diagnostic data high byte 25 I...

Страница 62: ...nit 0 L 1 ft3 1 Flow Reference Condition 0 STD 1 NOR 2 Flow rate diagnostic 0 Normal 1 HHH 3 Temperature diagnostic 0 Normal 1 HHH LLL 4 Pressure diagnostic 0 Normal 1 HHH LLL 5 Force AMS mode 0 No fo...

Страница 63: ...pressure value is below the specified value 0 Other than the above case 7 Pressure value over range HHH 1 The output pressure value exceeds the specified value 0 Other than the above case 8 Decline i...

Страница 64: ...ing Mismatch ID Mismatch Bit Description Details Value 0 ID Mismatch Connection device matching error 0 Match 1 Mismatch 1 Pdmapping Mismatch Process data mapping size error 0 In size 1 Exceeding size...

Страница 65: ...ssure low byte 10 System error Error Forced output Pressure diagnostic Temperature diagnostic Flow rate diagnostic Flow reference Condition Accumulated flow unit 11 AMS status 00HEX Initialising 01HEX...

Страница 66: ...byte 14 ITV diagnostic data high byte 15 ITV diagnostic data low byte 16 Reserved Port 3 short circuit VP short circuit Air Management Hub internal error 2 Air Management Hub internal error1 17 ITV P...

Страница 67: ...ced standby signal OFF 1 Forced standby signal ON 2 Isolation input signal for NC system Manual Isolation for NC System Available only if DIP switch configured as NC 0 Exhaust air ITV and VP_OFF 1 Sup...

Страница 68: ...this mode each function setting can be changed separately In measurement mode press the SET button for 3 seconds or longer to display F 0 Press the UP or DOWN button to select the function to be chang...

Страница 69: ...d value hold oFF Not stored Page 78 F33 Po_E Not Applicable on this product F40 FrtE Standby flow rate Threshold 25 AMS series 50 AMS30 series 100 AMS40 series 200 AMS60 series Page 79 FHyS Standby fl...

Страница 70: ...follows Standard condition Displayed flow rate which is converted to volume at 20 C 101 3 kPa absolute pressure Normal condition Displayed flow rate which is converted to volume at 0 C 101 3 kPa abso...

Страница 71: ...t the reference condition Press the SET button to set Units selection function Press the UP or DOWN button to select the display units 1 Flow rate Press the SET button to set 2 Temperature Press the S...

Страница 72: ...o select digital filter flow rate Select digital filter flow rate Press the UP or DOWN button to select the flow rate digital filter Press the SET button to set Move on to select digital filter pressu...

Страница 73: ...ressing the UP or DOWN button in function selection mode Press the SET button Move on to fine adjustment of display value Fine adjustment of display value Press the UP or DOWN button to change adjustm...

Страница 74: ...of the UP DOWN buttons are reversed Operation Display F13 by pressing the UP or DOWN button in function selection mode Press the SET button Move on to select reversed display Select reversed display P...

Страница 75: ...setting flow rate Press the UP or DOWN button to select the value of zero cut off The display above is an example of when L is selected for the PF3A801H 1000 L min type with the unit switching functio...

Страница 76: ...Displays 0 when the value is below 100 L min 200 to 4200 L min Displays 0 when the value is below 200 L min 6 0 0 to 6 F S 30 to 525 L min Displays 0 when the value is below 30 L min 60 to 1050 L min...

Страница 77: ...value is 0 029 to 0 029 MPa 4 0 0 to 4 F S 0 050 to 0 040 MPa 0 040 to 1 050 MPa Displays 0 when the value is 0 039 to 0 039 MPa 5 0 0 to 5 F S 0 050 MPa 0 050 to 1 050 MPa Displays 0 when the value i...

Страница 78: ...ting Measurement display setting Press the UP or DOWN button to select the measurement display setting 1 Pressure Press the SET button to set 2 Temperature Press the SET button to set 3 Accumulated fl...

Страница 79: ...14 3 years Data memorized every 2 minutes 2 minutes x 1 5 million times 3 million minutes 5 7 years If the Accumulated Flow External Reset is repeatedly used the product life will be shorter than calc...

Страница 80: ...Standby flow rate Hysteresis Set the value based on the setting method on page 81 Press the SET button Move on to Standby ON Delay Setting of Standby ON Delay Set the value based on the setting metho...

Страница 81: ...No PF OMA1007 Setting of auto isolation delay Set the value based on the setting method on page 81 Press the SET button to set Return to function selection mode F40 Complete setting for standby funct...

Страница 82: ...flashing 2 Press the UP or DOWN button to change the set value The UP button is to increase and the DOWN button is to decrease the set value Press the UP button once to increase the value by one digit...

Страница 83: ...nto the selected mode Operation Display F41 by pressing the UP or DOWN button in function selection mode Press the SET button Move on to the setting of Force AMS mode Setting of Force AMS mode Select...

Страница 84: ...on Move on to select display OFF mode Select display OFF mode Press the UP or DOWN button to select display OFF function Press the SET button to set Return to function selection mode F80 Setting of di...

Страница 85: ...e SET button to move to the digit to the right The default setting is 000 Press the SET button for 1 second or longer When the security code is correct move on to the security code setting If the secu...

Страница 86: ...T button for 1 second or longer At this point the changing of the security code is not completed Press the UP or DOWN button to return to setting step Press the SET button to set Return to function se...

Страница 87: ...OWN button For details of how to set each function refer to the relevant setting of function section in this manual Order of function settings Order Function Applicable model F0 Reference condition Al...

Страница 88: ...Air Management Hub can be checked Operation Display F96 by pressing the UP or DOWN button in function selection mode Press the SET button Move on to check cycle time Check cycle time Press the SET bu...

Страница 89: ...to select output check Select output check Press the UP or DOWN button to select the output check Move on to flow rate unit bit check Flow rate unit bit check Select the flow rate unit bit check by p...

Страница 90: ...c bit check Select the temperature diagnostic bit check by pressing the UP or DOWN button Press the SET button to set Pressure diagnostic bit check Select the pressure diagnostic bit check by pressing...

Страница 91: ...ror diagnosis bit check Select the system error diagnostic bit check by pressing the UP or DOWN button Press the SET button to set Accumulated value check Press the UP or DOWN button to select the acc...

Страница 92: ...to set Move on to pressure check Pressure check Press the UP or DOWN button to select the pressure check Press the SET button to set Return to function selection mode F98 Setting of output check comp...

Страница 93: ...e SET button Move on to reset to factory default settings Rest to factory default settings Press the UP or DOWN button to display ON then press the SET and DOWN buttons simultaneously for 5 seconds or...

Страница 94: ...e display indicated by the index part displayed by x106 or x103 If the DOWN button is pressed for 1 second the mantissa part will be displayed in 9 digits and the power value will be displayed as x103...

Страница 95: ...Each setting and peak bottom values are displayed using the UP and DOWN buttons Operation Without security code input 1 Press the SET button for 5 seconds or longer in measurement mode When oPE is di...

Страница 96: ...on then the security code is required When the security code is set select the un lock UnLoC using the UP or DOWN button Setting is recognized by pressing the SET button then the security code is requ...

Страница 97: ...tion is also recoverable to that prior to the power loss or de energizing However this may change depending on the operating environment Therefore check the safety of the whole installation before ope...

Страница 98: ...er supply voltage is in the range 24 VDC 10 1 Remove the noise and the noise source or take measures to prevent noise interference and reset the product or turn off and then turn back on the power sup...

Страница 99: ...the filter periodically Air leakage Check if air is leaking from the piping Rework the piping If the tightening torque is exceeded the mounting screws brackets and the flow switch may be damaged Warm...

Страница 100: ...original pressure etc Check the set value hysteresis Check the settings Incorrect wiring broken lead wire 1 Check the power supply wiring 2 Check if there is bending stress applied to any part of the...

Страница 101: ...hin the set pressure range Pressure below the lower limit of the set pressure range is applied Temperature error Temperature exceeding the upper limit of the set temperature range is applied Reset the...

Страница 102: ...ulated flow Press the DOWN and SET buttons simultaneously for 1 second or longer Zero clear error A pressure of 7 F S or more is applied during the zero clear operation Return to measurement mode in 1...

Страница 103: ...OUT connector is not used L A IN or L A OUT Green LED is ON LINK is established but data has not been received Check the following and restart 1 Check the PLC condition and run the PLC 2 Check that t...

Страница 104: ...orts 1 8 1 4 1 4 3 8 3 8 1 2 3 4 1 Applicable fluid Air Rated flow range 5 to 500 L min 10 to 1000 L min 20 to 2000 L min 40 to 4000 L min Operating fluid temperature 0 to 50 o C Proof pressure 1 0 MP...

Страница 105: ...1 8 1 4 1 4 3 8 3 8 1 2 3 4 1 Applicable fluid Air Rated flow range 5 to 500 L min 10 to 1000 L min 20 to 2000 L min 40 to 4000 L min Operating fluid temperature 0 to 50 o C Proof pressure 1 0 MPa Ra...

Страница 106: ...MPa standard Temperature characteristics 5 0 F S Ambient temp 0 to 50 o C 25 o C standard Units L min CFM ft3 min Pressure Rated pressure range 0 to 1 0 MPa Proof pressure 1 5 MPa Accuracy 3 0 F S Rep...

Страница 107: ...file GSDML file 3 EDS file 3 Occupation area Number of inputs outputs Max 512 byte 512 byte IP address setting range Through DHCP server Optional address Device information Vendor ID 7 SMC Corporation...

Страница 108: ...tics data Flow characteristics typical values AMS A Standby E P regulator type AMS20A Supply pressure 0 8 MPa Supply pressure 0 7 MPa Supply pressure 0 6 MPa Supply pressure 0 5 MPa Supply pressure 0...

Страница 109: ...108 No PF OMA1007 AMS30A Supply pressure 0 8 MPa Supply pressure 0 7 MPa Supply pressure 0 6 MPa Supply pressure 0 5 MPa Supply pressure 0 4 MPa Supply pressure 0 3 MPa...

Страница 110: ...109 No PF OMA1007 AMS40A Supply pressure 0 8 MPa Supply pressure 0 7 MPa Supply pressure 0 6 MPa Supply pressure 0 5 MPa Supply pressure 0 4 MPa Supply pressure 0 3 MPa...

Страница 111: ...110 No PF OMA1007 AMS60A Supply pressure 0 8 MPa Supply pressure 0 7 MPa Supply pressure 0 6 MPa Supply pressure 0 5 MPa Supply pressure 0 4 MPa Supply pressure 0 3 MPa...

Страница 112: ...111 No PF OMA1007 AMS B Standby regulator type Conditions Supply pressure 0 3 to 0 7 MPa Standby pressure 0 2 MPa Operation mode AMS20B AMS30B Rc1 4 Rx3 8 AMS40B AMS60B Rc1 2 Rc1...

Страница 113: ...112 No PF OMA1007 Conditions Supply pressure 0 3 to 0 7 MPa Standby pressure 0 2 MPa Standby mode 0 3 MPa 0 4 MPa 0 5 MPa 0 6 MPa 0 7 MPa AMS20B AMS30B Rc1 4 Rx3 8 AMS40B AMS60B Rc1 2 Rc1...

Страница 114: ...113 No PF OMA1007 Temperature Accuracy reference value Models A B AMS20 5 L min 500 L min AMS30 10 L min 1000 L min AMS40 20 L min 2000 L min AMS60 40 L min 4000 L min...

Страница 115: ...8 214 7 87 9 134 4 29 1 46 2 30 40 1 AMS40A C 3 8 1 2 334 8 214 9 92 4 151 6 32 6 46 2 36 40 1 AMS60A C 3 4 1 401 8 214 8 93 7 151 6 42 1 46 2 46 40 1 Part number Dimensions with bracket K F G H Q R S...

Страница 116: ...MA1007 AMS20 30 40 60A H00C Part number A F AMS20A H00C 219 9 68 6 AMS30A H00C 229 4 70 1 AMS40A H00C 264 4 86 6 AMS60A H00C 311 4 87 1 Refer to AMS20 30 40 60A R N F C for dimensions other than A and...

Страница 117: ...102 1 134 4 29 1 46 2 30 40 1 AMS40A D 3 8 1 2 334 8 214 9 119 4 151 6 32 6 46 2 36 40 1 AMS60A D 3 4 1 401 8 214 8 117 7 151 6 42 1 46 2 46 40 1 Part number Dimensions with bracket K F G H Q R S T U...

Страница 118: ...MA1007 AMS20 30 40 60A H00D Part number A F AMS20A H00D 219 9 68 6 AMS30A H00D 229 4 70 1 AMS40A H00D 264 4 86 6 AMS60A H00D 311 4 87 1 Refer to AMS20 30 40 60A R N F D for dimensions other than A and...

Страница 119: ...87 9 83 29 1 46 2 30 40 1 AMS40B C 3 8 1 2 395 8 214 9 92 4 88 32 6 46 2 36 40 1 AMS60B C 3 4 1 491 8 214 8 93 4 119 7 42 1 46 2 46 40 1 Part number Dimensions with bracket K F G H Q R S T U V W AMS2...

Страница 120: ...A1007 AMS20 30 40 60B H00C Part number A F AMS20B H00C 247 4 69 6 AMS30B H00C 285 9 83 1 AMS40B H00C 325 4 100 6 AMS60B H00C 401 4 121 1 Refer to AMS20 30 40 60B R N F C for dimensions other than A an...

Страница 121: ...102 1 83 29 1 46 2 30 40 1 AMS40B D 3 8 1 2 395 8 214 9 119 4 88 32 6 46 2 36 40 1 AMS60B D 3 4 1 491 8 214 8 118 119 7 42 1 46 2 46 40 1 Part number Dimensions with bracket K F G H Q R S T U V W AMS2...

Страница 122: ...A1007 AMS20 30 40 60B H00D Part number A F AMS20B H00D 247 4 69 6 AMS30B H00D 285 9 83 1 AMS40B H00D 325 4 100 6 AMS60B H00D 401 4 121 1 Refer to AMS20 30 40 60B R N F D for dimensions other than A an...

Страница 123: ...122 No PF OMA1007 Air Management Hub Base type EXA1 20 30 40 PN EN Model A B C D E F EXA1 20 236 2 35 42 19 1 65 1 30 5 EXA1 30 236 2 43 53 13 6 65 1 30 5 EXA1 40 240 4 51 64 4 4 6 71 35 5...

Страница 124: ...123 No PF OMA1007 EXA1 60 PN EN...

Страница 125: ...124 No PF OMA1007 Remote type EXA1 20 30 40 SA Model A B C D E F G EXA1 20 236 2 35 42 19 1 65 1 30 5 74 7 EXA1 30 236 2 43 53 13 6 65 1 30 5 74 7 EXA1 40 240 4 51 64 4 4 6 71 35 5 75 6...

Страница 126: ...125 No PF OMA1007 EXA1 60 SA Refer to separate operation manuals for other AMS components...

Страница 127: ...and mounted on each unit EX600 ZT1 Silencer Connect a silencer to the exhaust port on the residual pressure relief valve Recommended part numbers are shown below Part number Silencer Compact resin ty...

Страница 128: ...ion Connector With connector on both sides Plug Plug Plug connector pin arrangement D coded Plug connector pin arrangement D coded Item Specifications Cable O D 6 5 mm Conductor nominal cross section...

Страница 129: ...sides Plug Plug Plug connector pin arrangement D coded Plug connector pin arrangement D coded Item Specifications Cable O D 6 5 mm Conductor nominal cross section 0 34 mm2 AWG22 Wire O D Including in...

Страница 130: ...RJ 45 connector Plug RJ 45 connector Plug connector pin arrangement D coded Plug connector pin arrangement Item Specifications Cable O D 6 4 mm Nominal cross section 0 14 mm2 AWG26 Wire diameter 0 98...

Страница 131: ...OMA1007 Cable with connector Plug Plug connector pin arrangement D coded Item Specifications Cable O D 6 5 mm Nominal cross section AWG22 Wire diameter Including insulator 1 5 mm Min bending radius Fi...

Страница 132: ...ector pin arrangement D coded Applicable Cable Item Specifications Cable O D 4 0 to 8 0 mm Wire gauge Stranded wire cross section 0 14 to 0 34 mm2 AWG26 to 22 The table above shows the specifications...

Страница 133: ...132 No PF OMA1007 Power Supply Cable with M12 Connector A coded Socket connector pin arrangement A coded Normal key Plug connector pin arrangement A coded Normal key...

Страница 134: ...ZS 37 A Lead wire with M12 connector ZS 49 A Cable specification for M12 connector and lead wire ZS 37 A ZS 49 A Item Specifications Conductor Nominal cross section AWG23 Insulator O D Approx 1 1 mm C...

Страница 135: ...ctor cable for AMS components Lead wire with M12 connector EXA1 AC1 Cable specification for M12 connector and lead wire Item Specifications Conductor Nominal cross section AWG23 Insulator O D Approx 1...

Страница 136: ...PF OMA1007 Lead wire with M12 connector EXA1 AC2 Cable specification for M12 connector and lead wire Item Specifications Conductor Nominal cross section AWG23 Insulator O D Approx 1 1 mm Sheath Cable...

Страница 137: ...iyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL https www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manu...

Отзывы: