HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 44 of 69
No.
Type
Description
the upper and lower limits.
23
Fuel Pre-supply
Act in the period from crank to safety on time.
24
Generator Excite
Output in the crank process; output for 2s again if Gen
frequency is lost in high speed period.
25
Pre-lubricate
Act in the period from pre-heating to safety on time.
26
Remote Control
This port is controlled by communication (PC).
27
Reserved
28
Reserved
29
Close Generator
Control generator breaker to take load.
30
Open Breaker
Control generator breaker to take off load.
31
Reserved
32
Reserved
33
Start Relay
34
Fuel Relay
Act at generator start, disconnect at waiting to stop.
35
Idle Control
Used for gensets with idle speed control; Pull in before
crank, disconnect at entering warming up period; Pull
in at stop idle process, and disconnect at genset
complete stop.
36
Speed Raise Relay
Act in the period of warming up.
37
Speed Drop Relay
Act in the period of stop idle and wait to stop running time.
38
Energise to Stop
Used for engines with ETS electromagnet. Close when
stop idle is over and open when pre-
set ―ETS delay‖ is
over.
39
Speed Drop Pulse
Act for 0.1s when controller enters into stop idle, used
to control part of ECU dropping to idle speed.
40
ECU Stop
Used for ECU engine and control its stop.
41
ECU Power Supply
Used for ECU engine and control its power.
42
Speed Raise Pulse
Act for 0.1s when controller enters into warming up
delay; used to control part of ECU raising to normal
speed.
43
Crank Success
Close when a successful start signal is detected.
44
Generator OK
Act when generating is normal.
45
Generator Available
Act in period of generator ok to hi-speed cooling.
46
Reserved
47
Reserved
48
Common Alarm
Act at genset common warning, common shutdown,
common trips alarm.
49
Common Trip and Stop
Act when common trip and stop alarm occurs.
50
Common Shutdown
Act when common shutdown alarm occurs.
51
Common Trip
Act when common trips alarm occurs.
52
Common Warning
Act when common warning alarm occurs.
53
Reserved
54
Battery Over Voltage
Act when battery‘s over voltage warning alarm occurs.
55
Battery Under Voltage
Act when battery‘s low voltage warning alarm occurs.