HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 36 of 69
No.
Items
Parameters
Defaults
Description
voltage; start alarm handle when it is below
this value.
(0-3600)s
3
Alarm starts when voltage reaches alarm
value and this delay time is expired.
10
Over Freq.
Shutdown
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
114
Set value is percentage of AC Gen rated
freq. start alarm handle when it is above
this value.
(0-3600)s
2
Alarm starts when freq. reaches alarm
value and this delay time is expired.
11
Under Freq.
Shutdown
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
80
Set value is percentage of AC Gen rated
freq. start alarm handle when it is below
this value.
(0-3600)s
3
Alarm starts when freq. reaches alarm
value and this delay time is expired.
12
Over Volt. Warn
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
110
Set value is percentage of AC Gen rated
voltage; start alarm handle when it is
above this value.
(0~200)%
108
Set value is percentage of AC Gen rated
voltage; when alarm is active and voltage
is below return value, alarm can be cleared
automatically.
(0-3600)s
5
Alarm starts when voltage reaches alarm
value and this delay time is expired.
13
Under Volt.
Warn
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
84
Set value is percentage of AC Gen rated
voltage; start alarm handle when it is below
this value.
(0~200)%
86
Set value is percentage of AC Gen rated
voltage; when alarm is active and voltage
is above return value, alarm can be cleared
automatically.
(0-3600)s
5
Alarm starts when voltage reaches alarm
value and this delay time is expired.
14
Over Freq. Warn
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
110
Set value is percentage of AC Gen rated
freq. start alarm handle when it is above