HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 23 of 69
No.
Type
Action Range
Description
than the set value, and the reverse power
action select ―shutdown‖, it will send stop
signals.
15
AC Over Power
Shutdown
Active always
When controller detects reverse power value
of AC genset (power is positive) is higher
than the set value, and the reverse power
action select ―shutdown‖, it will send stop
signals.
16
DC Over Voltage
Active always
When controller detects the voltage value of
DC genset is higher than the set value, it will
send stop signals.
17
DC Under Voltage
Active from wait for load to
stop cooling
When controller detects the voltage value of
DC genset is lower than the set value, it will
send stop signals.
18
DC Over Current
Active always
When controller detects the current value of
DC genset is higher than the set value, it will
send stop signals.
19
DC Over Power
Shutdown
Active always
When controller detects reverse power value
of DC genset (power is positive) is higher
than the set value, and the reverse power
action select ―shutdown‖, it will send stop
signals.
20
Temp. Sensor Open
Active always
When controller detects sensor is open
circuit, and the action select ―shutdown‖, it
will send stop signals.
21
High Temp.
Shutdown
Active from start idle to
stop idle
When controller detects temperature is
higher than the set value, it will send stop
signals.
22
Pressure Sensor
Open
Active always
When controller detects sensor is open
circui
t, and the action select ―shutdown‖, it
will send stop signals.
23
Low Oil Pressure
Active from start idle to
stop idle
When controller detects oil pressure is lower
than the set value, it will send stop signals.
24
Level Sensor Open
Active always
When controller detects sensor is open
circuit, and the action select ―shutdown‖, it
will send stop signals.
25
Flexible Sensor 1
Open
Active always
When controller detects sensor is open
circuit, and the action select ―shutdown‖, it
will send stop signals.
26
Flexible Sensor 1
High
Active from start idle to
stop idle
When controller detects the sensor value is
higher than the max. set value, it will send
stop signals.
27
Flexible Sensor 1
Low
Active from start idle to
stop idle
When controller detects the sensor value is
lower than the min. set value, it will send