HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 52 of 69
8.4
SELECTION OF SENSORS
Table 16 - Sensors Selection
No.
Description
Remark
1
Temperature Sensor
0 Not Used
1 User Configured (Resistance)
2 User Config((4-20)mA) Curve
3 User Config.( 0-5V) Curve
4 VDO
5 CURTIS
6 VOLVO-EC
7 DATCON
8 SGX
9 SGD
10 SGH
11 PT100
12 SUSUKI
13 PRO
14~15 Reserved
Defined
resistance‘s
range is (0~6)
KΩ, default
is SGD sensor.
2
Pressure Sensor
0 Not Used
1 User Configured (Resistance)
2 User Config((4-20)mA) Curve
3 User Config.(0-5V) Curve
4 VDO 10Bar
5 CURTIS
6 VOLVO-EC
7 DATCON 10Bar
8 SGX
9 SGD
10 SGH
11 VDO 5Bar
12 DATCON 5Bar
13 DATCON 7Bar
14 SUSUKI
15 PRO
Defined
resistance‘s
range is (0~6)
KΩ, default
is SGD sensor.
3
Oil Level Sensor
0 Not used
1 User Configured (Resistance)
2 User Config((4-20)mA) Curve
3 User Config.(0-5V) Voltage Curve
4 SGD
5 SGH
6-15 Reserved
Defined
resistanc
e‘s
range is (0~6)
KΩ, default
is SGH sensor.
NOTE:
Above curve types are suitable for two flexible sensors, and the No.2 and No.3 items of fixed temperature/oil
pressure/ level sensor are configured as reserved.