HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 35 of 69
No.
Items
Parameters
Defaults
Description
than the set value, starter will be
disconnected. See the installation
instruction.
19
Disconnect Oil
Pressure
(0~1000)kPa
200
When generator oil pressure higher than
the set value, starter will be disconnected.
See the installation instruction.
AC Generator
1
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2
Poles
(2~64)
4
Numbers of generator pole, used for
calculating starter rotate speed when there
is not speed sensor.
3
Rated Voltage
(30~30000)V
230
To offer standards for detecting of
generator‘ over/under voltage and loading
voltage. It is primary voltage when using
voltage transformer.
4
Loading Voltage
(0~200)%
85
Setting value is AC generator rated
voltage‘s percentage. The controller
detects in the preparation of the load
period, and does not enter the normal
running period when the generator voltage
is less than the load voltage.
5
Rated Frequency
(10.0~600.0) Hz
50.0
To offer standards for detecting of
over/under/load frequency.
6
Loading
Frequency
(0~200)%
85
Setting value is AC generator rated
frequency
‘s percentage. The controller
detects in the preparation of the load
period, and does not enter the normal
running period when the generator voltage
is less than the load voltage.
7
PT Fitted
(0~1)
0
0: Disable; 1: Enable
Primary Voltage
(30-30000)V
100
Primary voltage of PT
Secondary
Voltage
(30-1000)V
100
Secondary voltage of PT
8
Over Volt.
Shutdown
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
120
Set value is percentage of AC Gen rated
voltage; start alarm handle when it is
above this value.
Alarm starts when voltage reaches alarm
value and this delay time is expired.
(0-3600)s
3
9
Under Volt.
Shutdown
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
80
Set value is percentage of AC Gen rated