HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 33 of 69
No.
Items
Parameters
Defaults
Description
7
Over Speed
Shutdown
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
114
Set value is percentage of rated speed;
start alarm handle when it is above this
value.
(0~3600)s
2
Alarm starts when speed reaches alarm
value and this delay time is expired.
8
Under Speed
Shutdown
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
80
Set value is percentage of rated speed;
start alarm handle when it is below this
value.
(0~3600)s
3
Alarm starts when speed reaches alarm
value and this delay time is expired.
9
Over Speed Warn
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
110
Set value is percentage of rated speed;
start alarm handle when it is above this
value.
(0~200)%
108
Set value is percentage of rated speed;
when alarm is active, and speed is below
return value, alarm can be cleared
automatically.
(0~3600)s
5
Alarm starts when speed reaches alarm
value and this delay time is expired.
10
Under Speed
Warn
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
86
Set value is percentage of rated speed;
start alarm handle when it is below this
value.
(0~200)%
90
Set value is percentage of rated speed;
when alarm is active, and speed is above
return value, alarm can be cleared
automatically.
(0~3600)s
5
Alarm starts when speed reaches alarm
value and this delay time is expired.
11
Battery Rated
Voltage
(0~60.0)V
24.0
Standard for detecting over/under voltage
of battery.
12
Battery Over
Volt Warn
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
120
Set value is percentage of battery voltage;
start alarm handle when it is above this
value.
(0~200)%
115
Set value is percentage of battery rated