HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 32 of 69
No.
Items
Parameters
Defaults
Description
Timers
1
Start Delay
(0~3600)s
1
Time from mains abnormal or remote start
signal is active to start genset.
2
Stop Delay
(0~3600)s
1
Time from mains normal or remote start
signal is deactivated to genset stop.
3
Preheat Delay
(0~3600)s
0
Time of pre-powering heat plug before
starter is powered up.
4
Cranking Time
(3~60)s
8
Time of starter power up
5
Crank Rest Time
(3~60)s
10
The waiting time before second power up
when engine start fail.
6
Safety On Delay (0~3600)s
10
Alarms for low oil pressure, high
temperature, under speed, under
frequency /voltage, charge fail are inactive.
7
Start Idle Time
(0~3600)s
0
Idle running time of genset when starting.
8
Warming Up
Time
(0~3600)s
10
Warming time between genset switch on
and normal running.
9
Cooling Time
(0~3600)s
10
Radiating time before genset stop, after it
unloads.
10
Stop Idle Time
(0~3600)s
0
Idle running time when genset stop.
11
ETS Solenoid
Hold
(0~3600)s
20
The time of powering up the electromagnet
during stop procedure.
12
Wait Stop Delay
(0~3600)s
0
Time between ending of genset idle delay
and stopped when ―ETS time‖ is set as 0;
Time between ending of ETS hold delay
and stopped when ―ETS Hold output time‖
is not 0.
13
After Stop Time
(0~3600)s
0
Time between genset stopped and standby
Engine
1
Engine Type
(0~39)
0
Default: Non ECU engine
When connected to J1939 engine, choose
the corresponding type.
2
Flywheel Teeth
(10~300)
118
Tooth number of the engine, for judging of
crank disconnect conditions and inspecting
of engine speed. See the installation
instructions.
3
Rated Speed
(0~6000)r/min
1500
Offer standard to judge over/under/loading
speed.
4
Speed On Load
(0~100)%
90
Setting value is percentage of rated speed.
Controller detects when it is ready to load.
It won‘t switch on when speed is under
loading speed.
5
Loss of Speed
Signal
(0~3600)s
5
Time from detecting speed is 0 to confirm
the action.
6
Action
(0~1)
0
0: Warning; 1: Shutdown