HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 38 of 69
No.
Items
Parameters
Defaults
Description
(1-36)
36
After IDMT is active, realize alarm delay by
setting this multiplier.
5
Reverse Power
0: Disable
1: Enable
0
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0-200)%
10
Set value is percentage of AC Gen rated
power; when power is negative and above
this value, start alarm handle.
(0-200)%
5
Set value is percentage of AC Gen rated
power; when alarm is active, power is
negative and below return value, alarm can
be cleared automatically.
(0-3600)s
5
Alarm starts when power reaches alarm
value and this delay time is expired.
6
Action
(0-3)
0
0: Warning; 1: Shutdown; 3: Trip and Stop;
4: Trip
7
Over Power
0: Disable
1: Enable
0
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0-200)%
110
Set value is percentage of AC Gen rated
power; when power is negative and above
this value, start alarm handle.
(0-200)%
105
Set value is percentage of AC Gen rated
power; when alarm is active, power is
negative and below return value, alarm can
be cleared automatically.
(0-3600)s
5
Alarm starts when power reaches alarm
value and this delay time is expired.
8
Action
(0-3)
0
0: Warning; 1: Shutdown; 3: Trip and Stop;
4: Trip
Breaker
1
Close Time
(0~20.0)s
5.0
Pulse width of generator switch on. When it
is 0, means output constantly.
2
Open Time
(0~20.0)s
3.0
Pulse width of generator switch off.
3
Check Time
(0~20.0)s
5.0
Time of detecting switch auxiliary contacts
after ATS breaker transferred.
4
Open Check
(0~1)
0
0: Disable 1: Enable
5
Check Fail Warn
(0~1)
0
0: Disable 1: Enable
Module
1
Power on Mode
(0~2)
0
0: Stop mode 1: Manual mode
2: Auto mode
2
Module Address
(1~254)
1
Controller‘s address during remote
sensing.
4
Language
(0~2)
0
0: Chinese 1: English 2: Other
5
Password
(0~65535)
00318
For entering parameters setting.
6
Time and Date
Current time and date can be set by users.