HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 37 of 69
No.
Items
Parameters
Defaults
Description
this value.
(0~200)%
108
Set value is percentage of AC Gen rated
freq. when alarm is active, and freq. is
below return value, alarm can be cleared
automatically.
(0-3600)s
5
Alarm starts when freq. reaches alarm
value and this delay time is expired.
15
Under Freq. Warn
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0-200)%
84
Set value is percentage of AC Gen rated
freq. start alarm handle when it is below
this value.
(0-200)%
86
Set value is percentage of AC Gen rated
freq. when alarm is active, and freq. is
above return value, alarm can be cleared
automatically.
(0-3600)s
5
Alarm starts when freq. reaches alarm
value and this delay time is expired.
16
Loss of Phase
(0~1)
1
0: Disable 1: Enable
17
Phase Sequence
Wrong
(0~1)
1
AC Load
1
Current
Transform
(5~6000)A/5A
500
The ratio of external CT
2
Rated Current
(5~6000)A
500
Generator‘s rated current, standard of load
current.
3
Rated Power
(0~6000)kW
276
Generator‘s rated power, standard of load
power.
4
Over Current
0: Disable
1: Enable
1
Start to detect alarms when it is enabled;
not detect alarms when disabled;
(0~200)%
120
Set value is percentage of AC Gen rated
full load current; Delay value can be set to
Definite Time or IDMT; Start alarm handle
when it is above this value.
0: Warn
1: Shutdown
2: Trip and Stop
3: Trip
0
Alarm type can be selected; when alarm is
active, it will start alarm handle according
to the selected alarm type.
Type: Definite
Time;
IDMT
Definite
Time
If Definite Time is set, then do alarm delay
handle by setting fixed delay time;
If IDMT is set, then do alarm delay handle
by setting multiplier;
(0-3600)s
10
After Definite Time is active, realize alarm
delay by setting this value.