HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 15 of 69
Table 7 - Power Factor Descriptions
★
DC GENS
, includes as below,
Voltage, current, power and accumulated energy
★
Alarm:
Displays all alarm information, including warning, alarm shutdown, trip shutdown and trip.
NOTE:
For ECU warning and shutdown alarms, if the detailed alarm information is displayed, check engine according to it,
otherwise, please check the manual of generator according to SPN alarm code.
★
Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or stop) and the real
time when alarm occurs.
★
Others
, includes,
Time and Date, count down time for maintenance, input/output ports status, NET status etc.
★
About,
includes,
Released software and hardware versions and PD number of controller
5.3.2
PARARMETERS SETTING MANUAL
Press
to enter user menu;
Configure
:
After entering the correct password (factory default password is 00318) you can enter
parameter settings screen.
Language
:
Selectable Chinese, English and others (default: Espanol)
Test Run
:
On load, off load and custom commissioning are optional. Custom commissioning can be
configured to on load or not during commissioning, commissioning time and which mode to return to
after commissioning (manual mode, auto mode and stop mode).
Clear accumula.
:
Can clear total running time A and B, total electric energy A and B.
5.3.3
PARAMETER SETTINGS
DC generator settings
Timers settings
Engine settings
AC Generator settings
AC Load settings
Breaker settings
Power factor Conditions Active power Inactive power
Remark
COS>0L
P>0,Q>0
Input
Input
Load is inductive resistance.
COS>0C
P>0,Q<0
Input
Output
Load is capacitance resistance.
COS<0L
P<0,Q>0
Output
Input
Load equals to one under excitation
generator
COS<0C
P<0,Q<0
Output
Output
Load equals to one over excitation
generator.
Remark:
1. Input active power, generator or mains supply electricity to load.
2. Output active power, load supply electricity to generator or mains.
3. Input reactive power, generator or mains send reactive power to load.
4.
Output reactive power, load send reactive power to generator or mains.