HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 42 of 69
No.
Items
Parameters
Defaults
Description
6
Description
LCD display detailed contents when the
input is active.
Digital Input Port 6
1
Contents Setting (0~55)
0
User defined .See Table 15
2
Active Type
(0~1)
0
0: Closed to Activate
1: Open to Activate
3
Arming
(0~3)
2
0: From safety on 1: From Crank
2: Always 3: Never
4
Active Actions
(0~4)
2
0: Warning; 1: Shutdown; 2: Trip and stop
3: Trip 4: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6
Description
LCD display detailed contents when the
input is active.
Digital Input Port 7
1
Contents Setting (0~55)
5
Lamp Test. See Table 15
2
Active Type
(0~1)
0
0: Closed to Activate
1: Open to Activate
Digital Input Port 8
1
Contents Setting
(0~55)
0
User Configured .See Table 15
2
Active Type
(0~1)
0
0: Closed to Activate
1: Open to Activate
3
Arming
(0~3)
0
0: From safety on 1: From Crank
2: Always 3: Never
4
Active Actions
(0~4)
0
0: Warning; 1: Shutdown; 2: Trip and stop
3: Trip 4: Indication
5
Active Delay
(0~20.0)s
2.0
Time from detecting active to confirm
6
Description
LCD display detailed contents when the
input is active.
Relay Outputs
Relay Output Port 1
1
Contents Setting (0~299)
1
Custom Period 1. See Table 14
2
Active Type
(0~1)
0
0: Output(N/O)
1: Output(N/C)
Relay Output Port 2
1
Contents Setting (0~299)
35
Idle Control See Table 14
2
Active Type
(0~1)
0
0: Output(N/O)
1: Output(N/C)
Relay Output Port 3
1
Contents Setting (0~299)
29
Close Generator. See Table 14
2
Active Type
(0~1)
0
0: Output(N/O)
1: Output(N/C)
Relay Output Port 4
1
Contents Setting (0~299)
31
Reserved. See Table 14
2
Active Type
(0~1)
0
0: Output(N/O)