HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 53 of 69
Table 17 - Crank Disconnect Conditions Selection
No.
Setting description
0
Gen frequency
1
Speed
2
Speed + Gen frequency
3
Oil pressure
4
Oil pr Gen frequency
5
Oil pr Speed
6
Oil pr Speed + Gen frequency
a) There are three kinds of separation conditions for starter and eninge, speed, frequency, and oil
pressure, all of which can be used separately. But it is suggested to use oil pressure, speed and
frequency together cooperatively, in order to make starter motor and engine separate as soon as
possible.
b) Speed sensor is the magnetic equipment installed on engine body to detect flywheel teeth number.
c) When speed is selected, please ensure engine flywheel teeth number is the same with the pre-set,
otherwise over speed shutdown or under speed shutdown may occur.
d) If speed sensor is not installed for genset, please don't select related items, otherwise failed to crank or
loss of speed signal shutdown may occur.
e) if oil pressure sensor is not installed for genset, please don't select related items.
f)
if Gen frequency is not selected for conditions, then controller doesn't collect and display related power
of Gens (can be used for pump genset); if speed is not selected, then the speed displayed on controller
is calculated by Gen signals.