HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 51 of 69
No.
Type
Description
21
Alarm Stop Inhibit
All shutdown alarms are prohibited except emergence
stop.(Means battle mode or override mode)
22
Instrument Mode
All outputs are prohibited in this mode.
23
Reserved
24
Reset Maintenance Alarm
Controller will set maintenance time and date as default when
input is active.
25
Reserved
26
High Temperature
Shutdown
Connected sensor digital input.
27
Low Oil Pressure
Shutdown
Connected sensor digital input.
28
Remote Start On Load
In
Auto
mode, when input is active, genset can be started
automatically and take load after genset normal running;
when input is inactive, genset will stop automatically.
29
Remote Start Off Load
In
Auto
mode, when input is active, genset can be started
automatically and NOT take load after genset normal running;
when input is inactive, genset will stop automatically.
30
Manual Start Input
In
Manual
mode, when input active, genset will start
automatically; when input inactive, genset will stop
automatically.
31
Reserved
32
Reserved
33
Simulate Stop Key
An external button can be connected and pressed as
simulate panel.
34
Simulate Manual Key
35
Reserved
36
Simulate Auto Key
An external button can be connected and pressed as
simulate panel.
37
Simulate Start Key
38
Simulate Generator Close
Key
39
Simulate Generator Open
Key
40
Reserved
41
Reserved
42
Reserved
43
Reserved
44
Reserved
45
Reserved
46
Reserved
47
Alt. Config. 1 Active
When input port is active, users can set different parameters
to make it easy to select current configuration via input port.
48
Alt. Config. 2 Active
49
Alt. Config. 3 Active
50-55
Reserved