Electrical installation
Instruction Manual FireGuard 2
13542E/4
37
Pos : 78 /F eldbussc hnit tst elle und Zusat z modul e/ Str omRel-Modul Übersic ht und Inst allati on mit SI PORT 2 @ 4\ mod_1441285797303_20.doc x @ 21514 @ 2 @ 1
5.7
StromRel module: Overview and installation
The configuration of the StromRel module is described in the Section 8.8.
In the
Digi.interf.
\
General
menu, the
Module type
must be set to
StromRel
and the
Module location
to
SIPORT 2
.
The current outputs can be loaded with up to 500 Ohm.
Using the semiconductor relay, currents up to 120 mA and voltages up to 50 V can be
connected.
The typical resistance when switched on is 20 Ohm. The switch is normally open.
A connection diagram can be found in the reference manual.
Figure 15: Overview of the StromRel module in the SIPORT 2
Interface for StromRel module
Connector for SIPORT 2 print
Terminals for StromRel module
(Cable cross-section: 0.08 ..
1.5 mm
2
)
The terminals of the StromRel module are configured as follows:
TERMINALS
FUNCTION
DESCRIPTION
1
mA 1 -
Current output 1
2
mA 1 +
3
mA 2 -
Current output 2
4
mA 2 +
5, 6
C1
Semiconductor relay 1
7, 8
C2
Semiconductor relay 2
9, 10
C3
Not available