Instruction Manual FireGuard 2
Mounting
26
13542E/4
Proceed as follows to install the mounting set:
WORKSTEP
ADDITIONAL INFO / IMAGES
1.
Position the completely assembled mounting
set in the bore hole.
The mounting set is delivered assembled
together with the FireGuard 2.
2.
Fasten the mounting set with pre-mounted
FireGuard 2 on the mounting flange (Figure 8,
pos. 3) with the three screws (circles).
A: Tunnel ceiling
The bore holes for fastening the mount-
ing set must be available.
3.
Align the photometer as follows:
1. Loosen the two fastening clips (Figure 8,
pos. 7).
2. Align the photometer in the direction of
travel.
The marking (X) must be aligned to the
flow direction (Y) of the tunnel.
3. Tighten the two fastening clips (Figure 8,
pos. 7) again.