Settings
Instruction Manual FireGuard 2
13542E/4
63
Pos : 134 /Bedi enung/FireGuard 2/M odus 2 FireG uar d 2 @ 4 \ mod_1449491691926_20. doc x @ 22704 @ 3 @ 1
8.3.3
Mode 2 (factory setting)
Mode 2 is active if one of the limits 5 .. 8 is active. Two limit levels are monitored. The four
states “Normal”, “Pre-alarm”, “Main alarm” and “Fault” are coded in binary. The following
table shows how the behavior of the outputs (O1/O2) can be influenced:
O1 Limit Invert
No
Yes
No
Yes
O2 Fault Invert
No
No
Yes
Yes
State
O2
O1
O2
O1
O2
O1
O2
O1
Normal
0
0
0
1
1
0
1
1
Alarm 1 (pre-alarm)
0
1
0
0
1
1
1
0
Alarm 2 (main alarm)
1
0
1
1
0
0
0
1
Fault
1
1
1
0
0
1
0
0
0 = high-resistance output
1 = low-resistance output
Bold
= factory setting
The
Fault
parameter on output 1 has no effect here. Limits 5 .. 8 are prioritized. If the
same event should be monitored on different levels on output 1 and 2, then it is absolutely
essential that the lower level (pre-alarm) is configured on output 1 and the higher level
(main alarm) is configured on output 2.