Servicing
Instruction Manual FireGuard 2
13542E/4
73
The following procedure describes how to clean the measuring cell on the FireGuard 2:
The photometer can be disassembled using an Allen wrench (size 7).
The screws must not be overtightened, as the thread may then be damaged.
Do
not exceed a tightening torque of 1 Nm
.
Check all removed parts for possible damages or signs of wear and replace with new
parts when necessary.
WORKSTEP
ADDITIONAL INFO / IMAGES
1.
Only carry out this step for installation in
suspended ceilings.
Loosen and swing away the two fastening clips
(circles). Lift the photometer out of the meas-
uring position.
2.
Remove and clean the contamination protec-
tion (circles).