Specifications:
Cat No.
643084 (Ionisation)
643085 (Photoelectric)
Supply Voltage
230-240V a.c.
Frequency
50Hz
Backup Battery
9V battery included (recommended
replacement: Energizer 522, Duracell
MN 1604 or MX 1604)
Temperature Range
+5
o
C to ~ +50
o
C
Humidity Range
10-95% at 20
o
C
Siren Sound Level
>
85 dB at 3 metres
Installation:
WARNING:
In the interests of safety, a licensed electrician, in accordance with
the relevant requirements of AS/NZS 3000, must install this smoke alarm and
all wiring.
This alarm must be wired to a continuous 230-240V a.c. 50Hz circuit. Ensure
any switching device cannot inadvertently override the unit.
NOTE:
See overleaf for recommended locations of alarms
INSTALLER PLEASE NOTE:
n
Before you connect the mains power, check wiring polarity.
n
If the alarm ‘chirps ’ press the Test button to check the battery condition.
Replace battery if necessary.
n
If ‘chirps ’ persist return smoke alarm to your supplier.
WIRING INSTRUCTIONS:
n
This smoke alarm can be interconnected with other 643084 or 643085
smoke alarms. Interconnection with other brands or models may cause
damage or result in a shock or fire risk.
n
Up to a limit of 20 smoke alarms may be interconnected.
n
Not interconnectable with HPM 645/3 ionisation smoke alarm
n
There are four terminals in the supply terminal block, marked A, I, N and
E/LOOP. It is important that the alarm be wired correctly to ensure correct
operation. Incorrect wiring to the smoke alarm will damage the unit and
invalidate the warranty. See wiring diagrams.
n
A maximum length of 300 metres of wire can be used in interconnecting
smoke alarms. Spacing between interconnected smoke alarms must not
exceed 30m per alarm.
n
Interconnected smoke alarms must be connected to the same final
sub-circuit.
n
Do not use any wire that could later be confused with the normal house
wires for the interconnect wire. For example, green/yellow earth wire.
n
Do not connect AC power wires to I interconnect terminal. This may
damage smoke alarms.
n
Do not connect the I interconnect wire to any device, except the
I interconnect terminal of another 643084 or 643085 smoke alarm or
interface 643086. Otherwise, smoke alarms will be damaged.
n
Smoke alarms should be interconnected only within the confines of a
single-family living unit. If smoke alarms are interconnected between
different units, there may be excessive nuisance alarms. Residents may not
be aware that smoke alarms are being tested or that it is a nuisance alarm
caused by cooking, etc.
PROFESSIONAL IONISATION / PHOTOELECTRIC SMOKE ALARM
INSTALLATION INSTRUCTIONS
IMPORTANT:
READ ALL INSTRUCTIONS BEFORE INSTALLATION.
NO USER SERVICEABLE PARTS INSIDE THIS SMOKE ALARM.
Do not attempt to repair the smoke alarm yourself.
I
A
N
I
A
N
E/LOOP
I
A
N
E/LOOP
40mm
10mm
CEILING / WALL JUNCTION
TYPICAL MULTIPLE
FLOOR INSTALLATION
SINGLE FLOOR
APEX OF
SLOPING
CEILING
CEILING
ACCEPTABLE HERE
BEDROOM
BEDROOM
BEDROOM
W/C
KITCHEN
DINING
BATH
BD/RM HALL
BD/RM
KITCHEN
RUMPUS
LOUNGE
ROOM
LOUNGE ROOM
Smoke alarms for minimum protection.
Smoke alarms for additional protection.
BEST
HERE
NEVER
HERE
HEAT &
SMOKE
FROM
FIRE
HEAT & SMOKE
FROM FIRE
DEAD AIR
SPACE
DEAD
AIR SPACE
SIDE WALL
300mm min
300mm mi
n
600mm mi
n
1500mm max
500mm mi
n
500m
m
min
BEST
HERE
BEST
HERE
THIS DEVICE CONTAINS A SMALL
AMOUNT OF RADIOACTIVE MATERIAL.
WARNING:
49mm
Ø147mm
Red LED
Green LED
84mm
50mm
84mm
84mm mounting
centre suitable for
standard mounting
brackets
Applicable to 643084 Ionisation alarm only.