background image

Green LED

  

AC Mains-ON Indicator:

 indicates that the unit is operating with AC power. If 

this LED goes out, it indicates that the AC power is off.

False Alarm Hush Control Feature:

  This smoke alarm has the capability of being temporarily desensitised for 

approximately 10 minutes.

  If the smoke alarm is sounding it can be desensitised by pressing the 

“HUSH/TEST” button on the smoke alarm cover.

  After pressing the “HUSH/TEST” button, the alarm will silence immediately 

and red LED will flash every 15 seconds for approximately 10 minutes to 

indicate the alarm is in the temporary desensitised condition.

  The smoke alarm will automatically reactivate after approximately 10 

minutes and sound the alarm if particles of combustion are still present.

  The “HUSH” feature may be used repeatedly until the air has cleared.

TESTING

NOTE: Before testing, make sure that the smoke alarm is connected to AC 

power supply (make sure the green LED is ON) and there is a 9V battery 

properly installed.

  Test alarm by pushing and holding the test “HUSH/TEST” button for 5  

seconds. This should sound the alarm if all electronic circuitry and horn are 

working.

  If no alarm sounds, check battery wiring, fuses or circuit breaker and make 

certain that alarm is connected to a continuous final sub-circuit.

  With interconnected units, holding test button down on one unit will cause 

all connected units to sound.

  Continuous chirping or erratic noise or low sound from an alarm may 

indicate a defective alarm.

Smoke alarm should be tested on a monthly basis. To accurately test the 

integrity of the sensing chamber use a smoke detector (aerosol) tester.

NOTE: 

After the above alarm test with the ‘HUSH/TEST’ button, the alarm will 

be desensitised for about 10 minutes. 

ONLY DO THE SMOKE AEROSOL TEST 

AFTER THIS DESENSITISED PERIOD.

WARNING: 

Do not apply excessive force on the “HUSH/TEST” button this may 

damage the smoke alarm and may void the warranty.

WARNING: 

Never use an open flame of any kind to test your alarm. You may 

damage the alarm or set fire to your home. The built-in test switch enables 

testing of all electronic components and the horn.

MAINTENANCE

The smoke alarm is virtually maintenance free. However, under dusty or 

greasy conditions, a vacuum cleaner may be used to clean the exterior of unit 

(including slots on cover). 

DO NOT IMMERSE IN OR SPRAY WITH HOUSEHOLD 

CLEANERS.

If the unit gives a chirping sound every 60sec the battery may need to be 

replaced.

Mounting Instructions:

1.

  Write down the date of installation on label provided.

2.

  Strip the Active/Neutral and Interconnect (if used) wires back to the strip 

length shown above.

3.

  Connect the wires to the correct terminals on the base as indicated and 

ensure the screws are fully tightened.

4.

  Clip the flap closed to prevent accidental contact with the live terminals.

5.

  Screw the mounting base to the ceiling or wall using the plugs and screws 

provided or No.6/No.8 superscrews.

6. 

 Install the 9V battery. The smoke alarm will not latch to the base unless 

battery is installed.

7. 

 Turn on the mains power and check the green and red LED function. Green 

LED should glow to show main power present. Red LED will pulse every 60 

seconds to indicate correct operation and the 9V battery is OK.

8.

  Press the Test/Hush button for 5 seconds to check the alarm works.

9.

  When installing onto a wall the mounting hinge must be on left hand side.

Battery:

BATTERY INSTALLATION

  The smoke alarm uses one 9V battery to automatically provide 

back-up power to the alarm if AC power fails. The battery will operate the 

alarm for approximately one to three months with AC power off.

   

USE ONLY BATTERIES AS SPECIFIED IN THE PRODUCT LABEL. USE OF A 

DIFFERENT BATTERY MAY HAVE A DETRIMENTAL EFFECT ON OPERATION 

OR MAY CAUSE THE BATTERY TO EXPLODE.

  

USE ONLY THE FOLLOWING 9-VOLT ALKALINE BATTERIES FOR 

REPLACEMENT: EVEREADY/ENERGIZER 522 DURACELL MN1604, MX1604

  Battery can only be inserted in one direction. Ensure polarity is correct.

BATTERY REPLACEMENT

  To replace battery, unlatch unit from mounting base and remove the battery 

from compartment. Replace the old battery with a fresh one and close unit. 

Verify that the green LED is on.

  To ensure proper operation, the battery should be replaced once a year.

  Smoke alarm cannot be closed properly without battery in place.

PROFESSIONAL IONISATION / PHOTOELECTRIC SMOKE ALARM

INSTALLATION INSTRUCTIONS

Installation:

n

     

Terminals at back of mounting base are marked as follows: 

A - Active         I - Interconnect         N - Neutral         E/Loop - Earth or Loop

EXAMPLE OF MULTIPLE ALARM WIRING:

When interconnected, all smoke alarms will sound upon activation. However, 

only the originating smoke alarm will have flashing Red LED.

WARNING: 

Connecting the Interconnect terminal to any supply conductor will 

result in damage to the alarm, failure to operate or shock hazard and will void 

the warranty of the alarm.

WARNING:

 Under no circumstances must an insulation resistance test be 

carried out on a circuit to which a smoke alarm is connected.
The test could cause irreparable damage to the internal circuitry of the smoke 

alarm and make it inoperative.
The warranty would be void under such circumstances.

I

A

N

I

A

N

E/LOOP

I

A

N

E/LOOP

40mm

10mm

CEILING / WALL JUNCTION

TYPICAL MULTIPLE

FLOOR INSTALLATION

SINGLE FLOOR

APEX OF
SLOPING
CEILING

CEILING

ACCEPTABLE HERE

BEDROOM

BEDROOM

BEDROOM

W/C

KITCHEN

DINING

BATH

BD/RM HALL

BD/RM

KITCHEN

RUMPUS

LOUNGE

ROOM

LOUNGE ROOM

Smoke alarms for minimum protection.
Smoke alarms for additional protection.

BEST
HERE

NEVER
HERE

HEAT &
SMOKE

FROM

FIRE

HEAT & SMOKE

FROM FIRE

DEAD AIR

SPACE

DEAD 

AIR SPACE

SIDE WALL

300mm min 

300mm mi

n

 600mm mi

n

1500mm max

500mm mi

n

500m

min

BEST
HERE

BEST
HERE

Operation, Testing and Maintenance:

OPERATION

The smoke alarm is operational once all wires are properly connected, the 

smoke alarm is correctly installed on the mounting base, battery inserted and 

the alarm has been tested. There are two LED indicators. Each of them has a 

unique function:

Red LED

  

Stand-by condition:

 will flash once approximately every 60 seconds to 

indicate unit is functioning properly.

  

Alarm condition:

 will flash quickly when unit goes into alarm. The flashing 

red LED and pulsating alarm will continue until the air is cleared. For 

interconnected units, the originating smoke alarm red LED will be flashing. 

All other units will sound but not flash.

Содержание 643084

Страница 1: ...nty See wiring diagrams n A maximum length of 300 metres of wire can be used in interconnecting smoke alarms Spacing between interconnected smoke alarms must not exceed 30m per alarm n Interconnected smoke alarms must be connected to the same final sub circuit n Do not use any wire that could later be confused with the normal house wires for the interconnect wire For example green yellow earth wir...

Страница 2: ...function Green LED should glow to show main power present Red LED will pulse every 60 seconds to indicate correct operation and the 9V battery is OK 8 Press the Test Hush button for 5 seconds to check the alarm works 9 When installing onto a wall the mounting hinge must be on left hand side Battery BATTERY INSTALLATION n The smoke alarm uses one 9V battery to automatically provide back up power to...

Страница 3: ...osed door may prevent the alarm from waking the sleeper n Smoke heat and other combustion products rise to the ceiling and spread horizontally Mounting the alarm on the ceiling in the centre of the room places it closest to all points in the room Ceiling mounting is preferred in ordinary residential construction n For mobile home installation select location carefully to avoid thermal barrier that...

Страница 4: ...anufactured or imported are of acceptable quality To make a claim under any statutory guarantee or other warranty you should first contact the supplier contractor or retailer from whom you purchased the products Customer Service For all Customer Service and Technical Support enquires please call Monday to Friday during business hours HPM Legrand Australia 1300 369 777 www legrand com au HPM Legran...

Отзывы: