Combination of metal and plastic pipes
Use straps for metal pipe and grounding rings for plastic pipe.
①
Metal pipe
②
Plastic pipe
Bonding/grounding straps, grounding rings and straps are not included in delivery.
Note
All straps or grounding wires must be 12 AWG (or heavier) copper wire and connected with 6
mm screws.
4.4
Cathodic-protected pipes
Pay special attention to meter installation in cathodic-protected pipe.
Isolate meter from pipeline by mounting isolation sleeves and washers on flange bolts and
connect a wire dimensioned to manage the cathodic current and environmental influence,
between pipelines.