4.1
Sensor installation
The sensor installation consists of three steps:
1. Locating the sensor.
2. Orienting the sensor.
3. Mounting the sensor.
4.1.1
Locating the sensor
Ensure that the sensor is located in the most optimum place and where no magnetic field is
present.
87L
166
N
S
Flow direction
Ensure that sensor is mounted in correct flow direction as indicated on label.
)ORZ
GLUHFWLRQ
If process flow direction is opposite of flow direction indicated on sensor label, forward flow
rates can be restored via parameter 327, if factor is adjusted to "-1".
MAG 8000 CT is approved for bidirectional measurement.
Installing/Mounting
4.1 Sensor installation
SITRANS MAG 8000
18
Operating Instructions, 11/2018, A5E03071515-AE