ID
Modifier
Command
Description
0x03
-
Query_Modes
-
0x01
List_Energy_Saving_Modes
Command for providing a list of supported energy saving modes.
0x02
Get_Mode
Command for supplying the parameter values with which the PE
energy saving function works (Page 88).
0x04
0x00
PEM_Status
Command for providing the status of the current energy saving
mode.
Result
After receiving the command, the 3RW5 soft starter sends the requested information, an error
message, or switches to the appropriate mode. When the mode is changed, the 3RW55 or
3RW55 Failsafe soft starter triggers a PROFIenergy status interrupt (Page 72).
8.1.2.1
Energy saving mode and operating mode
Modes
For data transmission, the 3RW5 soft starter distinguishes between two different states:
PE_Mode_ID = 255
Ready to operate (operating mode)
PE_Mode_ID = 01
Energy saving mode 1
Functions
8.1 PROFIenergy
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
85