Process data
Process image
3RW
50
1)
52
2)
55 /
55-F
3)
DI 3.6
New EX parameter values detected
-
-
x
5)
AI 4 (Float32)
Measured value 1
6)
(factory setting: Phase current I L1 (rms))
x
x
x
AI 8 (Float32)
Measured value 2
6)
(factory setting: Phase current I L2 (rms))
x
x
x
AI 12 (Float32)
Measured value 3
6)
(factory setting: Phase current I L3 (rms))
x
x
x
1)
Supported by SIRIUS 3RW50 soft starter
2)
Supported by SIRIUS 3RW52 soft starter
3)
Supported by SIRIUS soft starter 3RW55 and 3RW55 Failsafe
4)
3RW52 soft starter from firmware version V2.0
5)
3RW55 soft starter from firmware version V2.0 or 3RW55 Failsafe soft starter from firmware version V1.0
6)
You can parameterize the measured values for the 3RW55 and 3RW55 Failsafe soft starters. You will find additional
information in the Equipment Manual of the 3RW5 soft starter and in data set 135: Parameter cyclic process image. An
overview of the measured values can be found in the following table.
Data format Measured value
Unit
3RW
50
1)
52
2)
55
3)
55-F
4)
Float32
Phase current IL1 (rms)
A
x
x
x
x
Float32
Phase current IL2 (rms)
A
x
x
x
x
Float32
Phase current IL3 (rms)
A
x
x
x
x
Float32
Phase current average (rms)
A
-
-
x
x
Float32
Active energy import (total)
Wh
-
-
x
x
Float32
Active power
W
-
-
x
x
Float32
Power factor L1...3
-
-
-
x
x
1)
Supported by SIRIUS 3RW50 soft starter
2)
Supported by SIRIUS 3RW52 soft starter
3)
Supported by SIRIUS 3RW55 soft starter
4)
Supported by SIRIUS 3RW55 Failsafe soft starter
Process image output (PIQ)
Process data
Process image
3RW
50 /
52
1)
55
2)
55-F
3)
DQ 0.0
Motor CW
x
x
x
DQ 0.1
Motor CCW
-
x
x
DQ 0.3
Reset
4)
x
x
x
DQ 0.4
Emergency start
-
x
5)
x
5)
DQ 0.5
Self-test (user-test)
x
x
x
DQ 0.6
Creep speed
-
x
-
DQ 1.0
Output 1
6), 7)
-
x
x
DQ 1.1
Output 2
6), 7)
-
x
x
Appendix
A.3 Process data and process images
SIRIUS 3RW5 PROFINET communication modules
156
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004