Tag
NodeId.
Identifier
Data format Unit
Displayed name and level
Browse name
i =
1s
t
2n
d
3rd level
Active power
Active_Power_P
51
UInt32
W
Asymmetry
Phase_Unbalance
31
Byte
%
Motor temperature rise
Thermal_Memory
30
Byte
%
Phase current I L1 (%)
Current_I_L1
34
UInt16
%
Phase current I L2 (%)
Current_I_L2
35
UInt16
%
Phase current I L3 (%)
Current_I_L3
36
UInt16
%
Power factor L1...3
Cos_Phi
32
Byte
%
Remaining motor cooling time
Cooling_Down_Period
39
UInt16
s
Remaining time for motor overload
protection
Time_to_Trip
38
UInt16
s
Statistics
Statistics
2
-
-
Active energy import total
Consumed_Energy
92
UInt32
kWh
Last tripping current IA (%)
Last_Trip_Current
37
UInt16
%
Number of motor overload trips
Number_of_Overload_Trips
73
UInt16
-
Number of starts motor CCW
Int_Number_of_reverse_Starts
91
UInt32
-
Number of starts motor CW
Int_Number_of_direct_Starts
90
UInt32
-
Operating hours - device
Device_Operating_Hours
88
UInt32
s
Operating hours - motor
Motor_Operating_Hours
86
UInt32
s
Phase current max (%)
Max_Current_I_max
33
UInt16
%
8.5
Operation without PN control
The parameter "Operation without PN control" determines how the 3RW55 and 3RW55 Failsafe
soft starters behave in relation to a PLC. The parameter is only relevant in connection with the
use of the web server or OPC UA server.
Requirement
• 3RW5 PROFINET High Feature communication module from firmware version V2.0
• Soft starter 3RW55 with firmware version V2.1.1 or higher or soft starter 3RW55 Failsafe with
firmware version V1.1.0 or higher
Functions
8.5 Operation without PN control
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
135