1. Integrate the 3RW5 soft starter in the configuration software of the controller as the IO device
into the PROFINET IO system.
The following procedures are possible:
– Integrating 3RW5 soft starter via HSP in STEP 7 (TIA Portal) (Page 62)
– Integrating the 3RW5 Soft Starter into the PROFINET IO system with the GSDML file
(Page 63)
Note
STEP 7 (TIA Portal) as of V16
3RW5 soft starters, 3RW5 communication modules and 3RW5 HMIs are already contained in
the HW catalog of STEP 7 (TIA Portal) as of V16. Check the 3RW5 topic page for updates and
ensure that your device and the current firmware are contained in the HW catalog.
2. Enter a device name for the IO device in the configuration software of the controller (e.g. in
STEP 7 in the properties of the IO device).
Note the information in chapter Device name (Page 60).
3. Transfer the device name of the IO device online via the MAC address to the
3RW5 communication module (e.g. in STEP 7 in the "Assign device name" dialog box).
Note the information in chapter Device name (Page 60).
Note
Node flash test in STEP 7
Using the "Node flash test" (Page 70), you can quickly and easily identify the required IO
device, by getting the LEDs of the 3RW5 communication module to flash. Compare the MAC
address of the 3RW5 communication module with the displayed MAC address and select the
required IO device.
Alternatively, you can also set the device name via SIRIUS Soft Starter ES (TIA Portal)
Premium / Professional via fieldbus in the 3RW5 communication module.
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Online & Diagnostics" > Window "Work area" > "PROFINET IO ST / PROFINET IO HF >
Functions > Assign PROFINET device name"
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Device configuration" > Window "Work area" > Communication module "PROFINET IO ST /
PROFINET IO HF" > Inspector window "PROFINET IO ST / PROFINET IO HF" > Tab "Properties" >
Tab "General" > "PROFINET interface > Ethernet addresses > PROFINET"
4. Load the configuration into the IO controller.
5. Set the IP parameters in the 3RW5 communication module.
The following procedures are possible:
– During startup, the IO controller issues the IP parameters based on the device name and
assigns these to the IO device (temporary IP parameters).
– The IP parameters of the IO device are transferred online to the 3RW5 communication
module (static IP parameters).
Note the information in chapter IP parameters (Page 61).
Configuring
6.2 Configuring the 3RW5 Soft Starter
SIRIUS 3RW5 PROFINET communication modules
56
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004