Byte
Data format Maximum pointer
Value range
Incre‐
ment
3RW
50 /
52
1)
55 /
55-F
2)
16
Unsigned8
Maximum phase current I L1 (%)
0 … 796.9 %
3.125 % r
r
17
Unsigned8
Phase current I L2 max (%)
0 … 796.9 %
3.125 % r
r
18
Unsigned8
Phase current I L3 max (%)
0 … 796.9 %
3.125 % r
r
20
Unsigned16
Maximum trigger current
0 … 1 000 %
3.125 % r
r
22
Unsigned16
Number of motor overload trips
0 … 65 535
1
r
r
24
Signed32
Maximum trigger current
-20 000 … 20 000 A
0.01 A
r
r
28
Signed32
Minimum phase current I L1 (rms)
-20 000 … 20 000 A
0.01 A
r
r
32
Signed32
Phase current I L2 min (rms)
-20 000 … 20 000 A
0.01 A
r
r
36
Signed32
Phase current I L3 min (rms)
-20 000 … 20 000 A
0.01 A
r
r
40
Signed32
Maximum phase current I L1 (rms)
-20 000 … 20 000 A
0.01 A
r
r
44
Signed32
Phase current I L2 max (rms)
-20 000 … 20 000 A
0.01 A
r
r
48
Signed32
Phase current I L3 max (rms)
-20 000 … 20 000 A
0.01 A
r
r
52
Unsigned16
Line-to-line voltage U L1-L2 min
0 … 1 500 V
0.1 V
-
r
54
Unsigned16
Line-to-line voltage U L2-L3 min
0 … 1 500 V
0.1 V
-
r
56
Unsigned16
Line-to-line voltage U L3-L1 min
0 … 1 500 V
0.1 V
-
r
58
Unsigned16
Line-to-line voltage U L1-L2 max
0 … 1 500 V
0.1 V
-
r
60
Unsigned16
Line-to-line voltage U L2-L3 max
0 … 1 500 V
0.1 V
-
r
62
Unsigned16
Line-to-line voltage U L3-L1 max
0 … 1 500 V
0.1 V
-
r
69
Unsigned8
Maximum switching element heating
0 … 250 %
1 %
r
r
70
Unsigned8
Minimum line frequency
0 … 100 Hz
0.5 Hz
-
r
71
Unsigned8
Maximum line frequency
0 … 100 Hz
0.5 Hz
-
r
72
Unsigned32
Operating hours - motor current = 18 ... 49.9% x Ie 0 … 4 294 967 295 s 1 s
r
r
76
Unsigned32
Operating hours - motor current = 50 ... 89.9% x Ie 0 … 4 294 967 295 s 1 s
r
r
80
Unsigned32
Operating hours - motor current = 90 ... 119.9% x
Ie
0 … 4 294 967 295 s 1 s
r
r
84
Unsigned32
Operating hours - motor current = 120 ... 1000% x
Ie
0 … 4 294 967 295 s 1 s
r
r
88
Unsigned32
Operating hours - device
0 … 4 294 967 295 s 1 s
r
r
96
Signed32
Starting current I max (rms)
-20 000 … 20 000 A
0.01 A
r
r
100
Signed32
Starting current I L1 max (rms)
-20 000 … 20 000 A
0.01 A
r
r
104
Signed32
Starting current I L2 max (rms)
-20 000 … 20 000 A
0.01 A
r
r
108
Signed32
Starting current I L3 max (rms)
-20 000 … 20 000 A
0.01 A
r
r
112
Unsigned16
Number of starts with ext. bypass
0 … 65 535
1
r
r
3), 4)
114 ...
125
-
Reserved
-
-
-
-
1)
Supported by SIRIUS 3RW50 soft starter from firmware version V1.0 and 3RW52 from firmware version V2.0
2)
Supported by SIRIUS 3RW55 and 3RW55 Failsafe soft starters
3)
3RW55 soft starter from firmware version V2.0
4)
Not supported by SIRIUS 3RW55 Failsafe soft starter
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
176
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004