Error type
Inter‐
rupt
type
Error / Warning
Cause
+ F
1)
Byte.Bit
2)
0x1021
ER
Asymmetry
A limit value for asymmetry has been exceeded.
Asymmetry can cause an overload.
• Phase failure.
• Fault in the motor windings.
-
14.0
0x1021
MT
-
62.6
0x1022
ER
Therm. motor model over‐
load
• The motor feeder has been overloaded.
• The motor temperature rise has exceeded a lim‐
it.
x
12.3
0x1022
MT
-
62.3
0x1024
ER
Temperature sensor over‐
load
The temperature of the motor is too high.
x
12.0
0x1024
MT
-
22.5
0x1025
ER
Temperature sensor short
circuit
A short circuit has occurred in the temperature sen‐
sor cable.
x
12.2
0x1025
MT
-
22.7
0x1026
ER
Temperature sensor wire
break
A wire has broken in the sensor cable of the tem‐
perature sensor.
x
12.1
0x1026
MT
-
22.6
0x1027
ER
Ground fault
The ground-fault monitoring has responded. An
impermissibly high residual current is flowing.
-
16.0
0x1027
MT
-
62.7
0x1033
ER
No start-up data received
Data necessary for device start-up are missing.
-
18.4
0x1034
MT
Starting time exceeded
The set maximum starting time is shorter than the
starting time required by the motor.
-
92.2
0x1035
MT
Starting time undershot
The set minimum starting time is longer than the
starting time required by the motor.
-
92.3
0x1036
MT
Parameters for Ex motor pro‐
tection received
4)
Parameters for the EX motor protection have been
received.
-
60.2
0x1040
ER
Threshold I exceeded
The current has exceeded a limit.
-
14.2
0x1040
MT
-
62.4
0x1041
ER
Threshold I undershot
The current has undershot a limit.
-
14.3
0x1041
MT
-
62.5
0x1042
MT
Threshold P exceeded
The active power of the motor has exceeded a limit
value.
-
83.2
0x1042
ER
-
83.4
0x1043
MT
Threshold P undershot
The active power of the motor has undershot a limit
value.
-
83.3
0x1043
ER
-
83.5
0x1046
ER
Actuator disconnection
The module has disconnected the actuator. An ad‐
ditional diagnostic message will be displayed to
provide you with more detailed information about
the cause.
-
12.4
14.1
14.4
83.6
0x1057
ER
Number of switch-on opera‐
tions exceeded
The permissible number of switch-on operations in
the monitoring period has been exceeded.
x
71.1
0x1057
MT
-
71.3
0x1080
ER
Device error
Irrecoverable error detected following self-diagnos‐
tics (self-test, contactor contacts, switching ele‐
ment, etc.).
-
19.2
0x1081
ER
Bypass defective
• Bypass defective
• The error can also be generated by successive,
brief interruptions of the control supply voltage.
x
29.3
Messages and diagnostics
7.2 Diagnostics via configuration software of the controller
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
75