![Siemens SIRIUS 3RW5 series Скачать руководство пользователя страница 196](http://html.mh-extra.com/html/siemens/sirius-3rw5-series/sirius-3rw5-series_equipment-manual_1265469196.webp)
Byte
Bit
Data format
HMI diagnostics
3RW5
HMI HF
1)
12
0
Bool
FW update rejected
r
1
Bool
FW update active
r
2
Bool
FW update successful
r
3
Bool
FWUpdateUnsuccessful
r
4
Bool
FWUpdateInvalidSignature
r
13
0
Bool
Self-test active
r
2
Bool
Error during self-test
r
14
0
Bool
Device assigned
r
4
Bool
HMI not configured
r
18
0
Bool
Micro SD card active
r
1
Bool
Micro SD card access error
r
2
Bool
Micro SD card plugged
r
3
Bool
Micro SD card write-protected
r
19
0
Bool
LIActive
r
20
0
Bool
InvalidParameter
r
22
3
Bool
User account set up
r
23
0
Bool
No device answer
r
24
0
Bool
Write Error
r
25
0
Bool
Loading language rejected
2)
r
1
Bool
Loading language active
2)
r
2
Bool
Loading language successful
2)
r
3
Bool
Loading language unsuccessful
2)
r
4
Bool
Invalid signature 'Load additional language'
2)
r
26
0
Unsigned16
Faulty parameter number
3)
r
1)
Supported by 3RW5 HMI High Feature
2)
3RW5 HMI High Feature firmware version V3.0 or higher
3)
3RW5 HMI High Feature firmware version V2.0 or higher
A.4.6.2
Data set 131: HMI parameter (slot 3)
Read (r) and write (w) access to the HMI parameters is possible.
Byte
Data format
Meaning
3RW
50
1)
52
2)
55 /
55‑F
3)
0
Unsigned8
Coordination
[0x21] Write via acyclic bus channel – user program
x
x
x
2
Unsigned8
Slot number
x
x
x
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
196
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004