Procedure
1. Make sure that the motor is switched off and you do not start the motor during the firmware
update.
A control command for starting the motor is not supported during the firmware update.
To ensure the quickest and most fault-free firmware update, it is recommended that you
disconnect the main voltage (operating voltage) of the 3RW5 soft starter and set the
CPU / PLC to STOP mode.
2. Perform the update of the device firmware.
The following procedures are recommended:
– Via SIRIUS Soft Starter ES (TIA Portal) Premium / Professional on the 3RW5 communication
module
Brief overview: Window "Project Navigation" with current project under created Soft
Starter > "Online & Diagnostics" > Window "Work area" > "PROFINET IO ST /
PROFINET IO HF > Functions > Firmware update"
– Via the configuration software of the controller (e.g. STEP 7 with corresponding HSP) on
the 3RW5 communication module
Further procedures are possible:
– With a micro SD card via the 3RW5 HMI High Feature (Page 141)
– Via SIRIUS Soft Starter ES (TIA Portal) over the local interface on the 3RW5 HMI High
Feature
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
via 3RW5 communication module
Note
Firmware update of the 3RW5 PROFINET High Feature communication module
The firmware update of the 3RW5 PROFINET High Feature communication module via SIRIUS
Soft Starter ES (TIA Portal) at the local interface or using a Micro SD card via the 3RW5 HMI
High Feature can take a very long time (up to about 60 minutes).
Result
You have performed a firmware update for the 3RW5 communication module. The
3RW5 communication module restarts automatically.
Maintenance and service
9.1 Firmware update
SIRIUS 3RW5 PROFINET communication modules
140