Configuring
6
6.1
Configuring the 3RW5 Soft Starter in the PROFINET IO system
Requirements
• Mounted 3RW5 PROFINET communication module
3RW50 soft starters must also be connected to the 3RW5 communication module.
The 3RW5 soft starter automatically detects the presence of the 3RW5 communication
module when it is switched on.
• PROFINET IO system
– IO controller (programmable logic controller, e.g. SIMATIC S7‑1500)
– IO supervisor (PC or programming device)
– IO device (3RW5 PROFINET communication module)
• Configuration software of the controller, e.g. STEP 7 with HSP or GSDML file
• Parameterization software (optional), e.g. SIRIUS Soft Starter ES (TIA Portal) (Page 34)
• Basic knowledge of how to use PROFINET, e.g. for device name (Page 60) and IP parameter
(Page 61)
• Note the information in chapter Firmware update (Page 15).
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004