![Siemens SIRIUS 3RW5 series Скачать руководство пользователя страница 173](http://html.mh-extra.com/html/siemens/sirius-3rw5-series/sirius-3rw5-series_equipment-manual_1265469173.webp)
8)
Object number of the faulty parameter from data sets 131, 141, 151, 132, 142, 152, 133, 134 or 135
9)
3RW55 soft starter from firmware version V2.0
10)
3RW55 soft starter from firmware version V2.1
11)
Soft starter 3RW55 Failsafe with firmware version V1.1.0 or higher
12)
3RW55 soft starter from firmware version V2.1.1
A.4.5.4
Data set 94: Measured values
Only read (r) access to the measured values is possible.
Byte
Data format
Meaning
3RW
50
1)
52
2)
55 /
55-F
3)
0
Unsigned8
Coordination
x
x
x
2
Unsigned8
Slot number
x
x
x
4
Unsigned16
Length of data structure
x
x
x
6
Unsigned16
Start position
x
x
x
1)
Supported by SIRIUS 3RW50 soft starter
2)
Supported by SIRIUS 3RW52 soft starter
3)
Supported by SIRIUS soft starter 3RW55 and 3RW55 Failsafe
Byte
Data format Measured value
Value range
Incre‐
ment
3RW
50 /
52
1)
55 /
55-F
2)
12
Unsigned8
Phase current I L1 (%)
0 … 796.9 %
3.125 % r
r
13
Unsigned8
Phase current I L2 (%)
0 … 796.9 %
3.125 % r
r
14
Unsigned8
Phase current I L3 (%)
0 … 796.9 %
3.125 % r
r
16
Unsigned16
Remaining motor cooling time
0 … 1 800 s
0.1 s
r
r
19
Unsigned8
Asymmetry
0 … 100 %
1 %
-
r
20
Unsigned16
Motor temperature rise
0 … 1000 %
1 %
r
r
28
Unsigned8
Output frequency
0 … 100 Hz
0.5 Hz
-
r
32
Unsigned8
Line frequency
0 … 100 Hz
0.5 Hz
-
r
34
Unsigned16
Line-to-line voltage U L1-L2 (rms)
0 … 1 500 V
0.1 V
-
r
36
Unsigned16
Line-to-line voltage U L2-L3 (rms)
0 … 1 500 V
0.1 V
-
r
38
Unsigned16
Line-to-line voltage U L3-L1 (rms)
0 … 1 500 V
0.1 V
-
r
40
Signed32
Phase current I L1 (rms)
-20 000 … 20 000 A
0.01 A
r
r
44
Signed32
Phase current I L2 (rms)
-20 000 … 20 000 A
0.01 A
r
r
48
Signed32
Phase current I L3 (rms)
-20 000 … 20 000 A
0.01 A
r
r
55
Unsigned8
Switching element heating
0 … 250 %
1 %
r
r
56
Unsigned16
Remaining switching element cooling time
0 … 1 800 s
0.1 s
r
r
58
Unsigned16
Remaining time for motor overload protection
0 … 6 500 s
0.1 s
-
r
60
Signed32
Active power
-2 147.483 …
2 147.483 kW
0.0001
kW
-
r
66
Unsigned8
Power factor L1...3
0 … 1
0.01
-
r
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
173