4 Technical Data
444
7UM62 Manual
C53000-G1176-C149-3
4.29
Breaker Failure Protection (ANSI 50BF)
Pickup and Delay
Time Ranges/
Resolutions
Pickup of 50 Element
BF.I>
0.20 A to 10.00 A
1
)(Increments 0.05 A)
1
)
Delay Time
TRIP-Timer
0.06 s to 60.00 s
(Increments 0.01 s)
or
∞ (
no trip)
Initiating Time
Pickup Times (protection initiates)
- For Internal Start
Approx. 50 ms
- Using Controls
Approx. 50 ms
- For External Start
Approx. 50 ms
Reset Time
Approx. 50 ms
Tolerances
Pickup Current
BF.I>
1 % of set value, or 50 mA
1
)
Delay Time
TRIP-Timer
1 % or 10 ms
Influencing
Variables
Power Supply DC voltage (U
DC
) in Range
0.8
≤
U
PS
/ U
PS nominal
≤
1.15
1 %
Temperature in Range
23 °F
≤ ϑ
amb
≤
131 °F
0.3 % / 10 °F
–5 °C
≤ ϑ
amb
≤
55 °C
0.5 % / 10 K
Frequency in Range
0.95
≤
f/f
N
≤
1.05
< 1 %
Harmonic currents
– Up to 10 % 3. Harmonic
< 1 %
– Up to 10 % 5. Harmonic
< 1 %
1
) For I
N
= 1 A, divide all limits and increments by 5.