4.26 Sensitive Rotor Earth Fault Protection with 1 to 3 Hz (ANSI 64R)
441
7UM62 Manual
C53000-G1176-C149-3
4.26
Sensitive Rotor Earth Fault Protection with 1 to 3 Hz (ANSI 64R)
Setting Ranges/
Resolution
Warning Stage
R
E WARN
5 k
Ω
to 80 k
Ω
(Increments 1 k
Ω
)
Tripping Stage
R
E TRIP
1 k
Ω
to 10 k
Ω
(Increments 1 k
Ω
)
Delay Time
0.00 s to 60.00 s
(Increments 0.01 s)
or
∞
(does not expire)
Pickup Value of
Q
C
<
0.01 to 1.00 mAs
(Increments
Open Rotor Circuit
0.01 mAs)
Inherent Operating
Times
Pickup Time
Approx. 1 to 1.5 s (depends on 7XT71)
Dropout Time
Approx. 1 to 1.5 s
Dropout
Resistance R
E
Approx. 1.25
Charge Q
C
<
1.2 or 0.01 mAs
Tolerances
Resistance
Approx. 5 % or 0.5 k
Ω
at 0.15 µF
≤
C
E
< 1 µF
Approx. 10 % or 0.5 k
Ω
at 1 µF
≤
C
E
< 3µF
Charge
5 % or 0.005 mAs
Delay Time
1 % or 10 ms
Permissible Rotor-Earth Capacitance
0.15 to 3 µF
Influencing
Variables for
Pickup
Power Supply Direct Voltage in Range
0.8
≤
U
H
/U
HN
≤
1.15
≤
1 %
Temperature in Range
–5 °C
≤ ϑ
amb
≤
55 °C
≤
0.5 %/10 K
Frequency in Range
0.95
≤
f/f
N
≤
1.05
≤
1 %
Harmonics
– Up to 10 % 3rd Harmonics
≤
1 %
– Up to 10 % 5th Harmonics
≤
1 %