Temperature Detection by Thermoboxes
273
7UM62 Manual
C53000-G1176-C149-3
2.42.2.1 Settings of the Temperature Detection Function
Addr.
Setting Title
Setting Options
Default Setting
Comments
9011A
RTD 1 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
Pt 100 Ohm
RTD 1: Type
9012A
RTD 1 LOCATION
Oil
Ambient
Winding
Bearing
Other
Winding
RTD 1: Location
9013
RTD 1 STAGE 1
-50..250
°
C;
∞
100
°
C
RTD 1: Temperature Stage 1
Pickup
9014
RTD 1 STAGE 1
-58..482
°
F;
∞
212
°
F
RTD 1: Temperature Stage 1
Pickup
9015
RTD 1 STAGE 2
-50..250
°
C;
∞
120
°
C
RTD 1: Temperature Stage 2
Pickup
9016
RTD 1 STAGE 2
-58..482
°
F;
∞
248
°
F
RTD 1: Temperature Stage 2
Pickup
9021A
RTD 2 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 2: Type
9022A
RTD 2 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 2: Location
9023
RTD 2 STAGE 1
-50..250
°
C;
∞
100
°
C
RTD 2: Temperature Stage 1
Pickup
9024
RTD 2 STAGE 1
-58..482
°
F;
∞
212
°
F
RTD 2: Temperature Stage 1
Pickup
9025
RTD 2 STAGE 2
-50..250
°
C;
∞
120
°
C
RTD 2: Temperature Stage 2
Pickup
9026
RTD 2 STAGE 2
-58..482
°
F;
∞
248
°
F
RTD 2: Temperature Stage 2
Pickup
9031A
RTD 3 TYPE
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 3: Type
9032A
RTD 3 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 3: Location
9033
RTD 3 STAGE 1
-50..250
°
C;
∞
100
°
C
RTD 3: Temperature Stage 1
Pickup
9034
RTD 3 STAGE 1
-58..482
°
F;
∞
212
°
F
RTD 3: Temperature Stage 1
Pickup