4 Technical Data
438
7UM62 Manual
C53000-G1176-C149-3
4.23
100–%–Stator Earth Fault Protection with 3rd Harmonics
(ANSI 27/59TN 3rd Harm.)
Setting Ranges/
Resolutions
Pick–Up Value for 3rd Harmonic
in Undervoltage Stage
U
0 (3rd HARM)
< 0.2 V to 40.0 V
(Increments 0.1 V)
Pick–Up Value for 3rd Harmonic
in Overvoltage Stage
U
0 (3rd HARM)
> 0.2 V to 40.0 V
(Increments 0.1 V)
Delay Time
T
SEF (3rd HARM)
0.00 s to 60.00 s
(Increments 0.01 s)
oder
∞
(does not expire)
Release Threshold
P/Pmin >
10 % to 100 %
(Increments 1 %)
or 0 (ineffective)
U/U
1 min
>
50.0 V to 125.0 V (Increments 0.1 V)
or 0 (ineffective)
Inherent Operating
Times
– Pickup Times
Approx. 80 ms
– Dropout Times
Approx. 80 ms
Dropout
Undervoltage Stage
U
0 (3rd HARM)
< Approx. 1.10 or 0.1 V
Overvoltage Stage
U
0 (3rd HARM)
> Approx. 0.90 or 0.1 V
Release Thresholds
P/P
min
>
Approx. 0.90
U/U
1 min
>
Approx. 0.95
Tolerances
– Displacement Voltage
3 % of setting value or 0.1 V
– Delay Time
T
SEF (3rd HARM)
1 % of setting value or 10 ms
Influencing
Variables for
Pickup
Power Supply Direct Voltage in Range
0.8
≤
U
PS
/ U
PS nominal
≤
1.15
1 %
Temperature in Range
23 °F
≤ ϑ
amb
≤
131 °F
0.3 % / 10 °F
–5 °C
≤ ϑ
amb
≤
55 °C
0.5 % / 10 K
Frequency in Range
0.95
≤
f/f
N
≤
1.05
< 1 %