A Appendix
526
7UM62 Manual
C53000-G1176-C149-3
1401
O/C Ip
Inverse O/C
Time Protection
OFF
ON
Block relay for trip
commands
OFF
Inverse O/C Time Protec-
tion Ip
1402
Ip
Inverse O/C
Time Protection
0.10..4.00 A
1.00 A
Ip Pickup
1403
T Ip
Inverse O/C
Time Protection
0.05..3.20 sec;
∞
0.50 sec
T Ip Time Dial
1404
TIME DIAL: TD
Inverse O/C
Time Protection
0.50..15.00;
∞
5.00
TIME DIAL: TD
1405
IEC CURVE
Inverse O/C
Time Protection
Normal Inverse
Very Inverse
Extremely Inverse
Normal Inverse
IEC Curve
1406
ANSI CURVE
Inverse O/C
Time Protection
Very Inverse
Inverse
Moderately Inverse
Extremely Inverse
Definite Inverse
Very Inverse
ANSI Curve
1407
VOLT. INFLU-
ENCE
Inverse O/C
Time Protection
without
Voltage controlled
Voltage restraint
without
Voltage Influence
1408
U<
Inverse O/C
Time Protection
10.0..125.0 V
75.0 V
U< Threshold for Release
Ip
1601
Ther. OVER LOAD
Thermal Over-
load Protection
OFF
ON
Block relay for trip
commands
Alarm Only
OFF
Thermal Overload Protec-
tion
1602
K-FACTOR
Thermal Over-
load Protection
0.10..4.00
1.11
K-Factor
1603
TIME CONSTANT
Thermal Over-
load Protection
30..32000 sec
600 sec
Thermal Time Constant
1604
Θ
ALARM
Thermal Over-
load Protection
70..100 %
90 %
Thermal Alarm Stage
1605
TEMP. RISE I
Thermal Over-
load Protection
40..200
°
C
100
°
C
Temperature Rise at Rated
Sec. Curr.
1606
TEMP. RISE I
Thermal Over-
load Protection
104..392
°
F
212
°
F
Temperature Rise at Rated
Sec. Curr.
1607
TEMP. INPUT
Thermal Over-
load Protection
Disabled
4-20 mA
Fieldbus
Temp. of RTD 1
Disabled
Temperature Input
1608
TEMP. SCAL.
Thermal Over-
load Protection
40..300
°
C
100
°
C
Temperature for Scaling
1609
TEMP. SCAL.
Thermal Over-
load Protection
104..572
°
F
212
°
F
Temperature for Scaling
1610A I ALARM
Thermal Over-
load Protection
0.10..4.00 A
1.00 A
Current Overload Alarm
Setpoint
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments