![Siemens SIPROTEC 7UM62 Скачать руководство пользователя страница 551](http://html.mh-extra.com/html/siemens/siprotec-7um62/siprotec-7um62_manual_382677551.webp)
A.12 Settings
535
7UM62 Manual
C53000-G1176-C149-3
4514
df4/dt >/<
Rate-of-fre-
quency-change
protection
-df/dt< negative rate
of freq. change
+df/dt> positive rate
of freq. change
-df/dt< negative rate
of freq. change
Mode of Threshold (df4/dt
>/<)
4515
STAGE df4/dt
Rate-of-fre-
quency-change
protection
0.1..10.0 Hz/s;
∞
4.0 Hz/s
Pickup Value of df4/dt
Stage
4516
T df4/dt
Rate-of-fre-
quency-change
protection
0.00..60.00 sec;
∞
0.00 sec
Time Delay of df4/dt Stage
4517
df4/dt & f4
Rate-of-fre-
quency-change
protection
OFF
ON
OFF
AND logic with pickup of
stage f4
4518
U MIN
Rate-of-fre-
quency-change
protection
10.0..125.0 V; 0
65.0 V
Minimum Operating
Voltage Umin
4519A df1/2 HYSTERES.
Rate-of-fre-
quency-change
protection
0.02..0.99 Hz/s
0.10 Hz/s
Reset Hysteresis for df1/dt
& df2/dt
4520A df1/2 M-WINDOW
Rate-of-fre-
quency-change
protection
1..25 Cycle
5 Cycle
Measuring Window for df1/
dt & df2/dt
4521A df3/4 HYSTERES.
Rate-of-fre-
quency-change
protection
0.02..0.99 Hz/s
0.40 Hz/s
Reset Hysteresis for df3/dt
& df4/dt
4522A df3/4 M-WINDOW
Rate-of-fre-
quency-change
protection
1..25 Cycle
5 Cycle
Measuring Window for df3/
dt & df4/dt
4601
VECTOR JUMP
Jump of Voltage
Vector
OFF
ON
Block relay for trip
commands
OFF
Jump of Voltage Vector
4602
DELTA PHI
Jump of Voltage
Vector
2..30
°
10
°
Jump of Phasor DELTA
PHI
4603
T DELTA PHI
Jump of Voltage
Vector
0.00..60.00 sec;
∞
0.00 sec
T DELTA PHI Time Delay
4604
T RESET
Jump of Voltage
Vector
0.10..60.00 sec;
∞
5.00 sec
Reset Time after Trip
4605A U MIN
Jump of Voltage
Vector
10.0..125.0 V
80.0 V
Minimal Operation Voltage
U MIN
4606A U MAX
Jump of Voltage
Vector
10.0..170.0 V
130.0 V
Maximal Operation Voltage
U MAX
4607A T BLOCK
Jump of Voltage
Vector
0.00..60.00 sec;
∞
0.10 sec
Time Delay of Blocking
5001
S/E/F PROT.
Stator Earth
Fault Protection
OFF
ON
Block relay for trip
commands
OFF
Stator Earth Fault Protec-
tion
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments