Functional Scope
21
7UM62 Manual
C53000-G1176-C149-3
For the differential protection, address
allows to specify the type
of protected object (
Generator/Motor
or
3-phase Transformer
); the function
can be excluded altogether by setting
Disabled
.
Figure 2-2
Use as Generator Differential Protection
Figure 2-3
Use as Block Differential Protection (Overall Protection)
For the following application, the settings of the generator data under Power System
Data 1 must be same as for the transformer data of side 2:
Figure 2-4
Use as Transformer Differential Protection
7UM62
G
3
∼
Side 2
Side 1
Address
Generator/Motor
7UM62
G
3
∼
Side 2
Side 1
Address
3-phase Transformer
7UM62
G
3
∼
Side 1
Address
=
3-phase Transformer
Side 2