![Siemens SIPROTEC 7UM62 Скачать руководство пользователя страница 414](http://html.mh-extra.com/html/siemens/siprotec-7um62/siprotec-7um62_manual_382677414.webp)
4 Technical Data
398
7UM62 Manual
C53000-G1176-C149-3
– Transmission Speed
Min. 4800 Baud; max. 115200 Baud
Factory Setting: 38400 Baud; Parity: 8E1
– Maximum Distance of Transmission
15 meters / 49 feet
Rear Service–/
Modem– Interface
– Connection
Isolated interface for data transfer
– Operation
With DIGSI
®
4
– Transmission Speed
Min. 4800 Bd, max. 38400 Bd
Factory Setting: 38400 Bd
RS232/RS485
Depends on order code
– Connection for Flush Mounted case
Rear panel, mounting location “C“
9-pin DSUB port
for Panel-Surface
At the terminal on the case bottom
Mounted Case
– Test Voltage
500 VAC
RS232
– Maximum Distance of Transmission
15 meters / 49 feet
RS485
– Maximum Distance of Transmission
1 km / 3280 feet / 0.62 mile
SCADA Interface
IEC 60870–5–103
RS232/RS485
Floating interface for data transfer
Depends on order code
to a master terminal
RS232
– Connection for Flush Mounted Case
Rear panel, mounting location “B“
9-pin DSUB port
For Panel Surface-
At the terminal on the case bottom
Mounted Case
– Test Voltage
500 VAC
– Transmission Speed
Min. 4800 Bd, max. 38400 Bd
Factory Setting: 38400 Bd
– Maximum Distance of Transmission
15 meters / 49 feet
RS485
– Connection for Flush Mounted Case
rear panel, installation location “B“
9-pin DSUB Port RS 485
For Panel Surface-
at the terminal on the case bottom
Mounted Case
Profibus cable
– Test Voltage
500 VAC
– Transmission Speed
Min. 4800 Bd, max. 38400 Bd
Factory Setting: 38400 Bd
– Maximum Distance of Transmission
1 km / 3280 feet / 0.62 mile
Fibre Optical Link
– Connector Type
ST–Connector
With Flush-Mounted Case
Rear panel, mounting location “B“