The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
dM/dt rise (/Filter
time)
and can be adjusted.
Application and Setting Notes - V1 Trigger (Positive-Sequence System)
Parameter: Mode
•
Default setting
(_:9661:1) Mode
=
off
With the
Mode
parameter, you activate the trigger for normal operation (On) or the test mode (Test).
Parameter Value
Description
on
The function block V1 Trigger is activated and the voltage in the positive-
sequence system is monitored on the basis of the set trigger parameter.
off
The function block V1 Trigger is deactivated.
test
The function block V1 Trigger is activated for test purposes.
Parameter: Max. Trigger Active/Max. Trigger/Max. Trigger Hysteresis
•
Default setting
(_:9661:101) Max. trigger active
=
yes
•
Default setting
(_:9661:105) Max. trigger
=
69.284 V
•
Default setting
(_:9661:113) Max. trigger hysteresis
=
0.980 p.u.
With the
Max. trigger active
parameter, you activate the level trigger in order to monitor the voltage in
the positive-sequence system and to prevent it from exceeding the set values.
Parameter Value
Description
yes
The voltage in the positive-sequence system is monitored for overvoltage.
no
The voltage in the positive-sequence system is not monitored for over-
voltage.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
Max. trigger
and can
be adjusted.
Parameter: Min. Trigger Active/Min. Trigger/Min Trigger Hysteresis
•
Default setting
(_:9661:102) Min. trigger active
=
yes
•
Default setting
(_:9661:106) Min. trigger
=
46.189 V
•
Default setting
(_:9661:114) Min. trigger hysteresis
=
1.020 p.u.
With the
Min. trigger active
parameter, you activate the level trigger in order to monitor the voltage in
the positive-sequence system and to prevent ut from dropping below the set value.
Parameter Value
Description
yes
The voltage in the positive-sequence system is monitored for undervoltage.
no
The voltage in the positive-sequence system is not monitored for under-
voltage.
The hysteresis is preset at the factory to 1.020 p.u. (equal to 2 %) of the parameter
Min. trigger
and can
be adjusted.
Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
•
Default setting
(_:9661:103) dM/dt rise active
=
no
•
Default setting
(_:9661:107) dM/dt rise (/Filter time)
=
11.547 V
•
Default setting
(_:9661:115) dM/dt rise hysteresis
=
0.980 p.u.
•
Default setting
(_:9661:112) Filter time
=
2 periods
7.5.1.7
Fault Recorder
7.5 Trigger Functions 3-Phase
306
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...