i
i
NOTE
The
Mode
of the individual recorder depends on the settings of the parameter
Mode
in the higher-level
function General.
The status of the function resulting from the parameter
Mode
and the superordinate state of the recorder is
shown in the following table.
Table 7-1
Resulting State of the Function (from Connection of Parameter Mode and Superordinate State)
Mode
State of the
Recorder
Mode
State of the
Recorder
Mode
State of the
Recorder
General Function
(Superordinate State)
On
Off
Test
Individual recorder
On
On
On
Off
On
Test
Individual recorder
Off
Off
Off
Off
Off
Off
Individual recorder
Test
Test
Test
Off
Test
Test
i
i
NOTE
Every change of a recorder parameter (with the exception of changing the mode and trigger parameters)
results in a restart of the device.
i
i
NOTE
A currently existing trigger violation does not trigger fault records if
•
the device is restarted
•
the device, the recording, or the mode of the recorder is switched from
on
to
off
.
Configuring Trigger Routing
You can route triggers to recorder instances. A trigger can be routed to one or more recorder instances. To
generate a fault record, assign the triggers to the recorders.
²
Double-click Recorder interaction in the project tree in DIGSI 5.
²
Right-click X (routed).
Fault Recorder
7.1 Introduction to DIGSI 5
224
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...