No.
Information
Data Class
(Type)
Type
_:11611:60
Sensor 12:Failure
SPS
O
_:11611:80
Sensor 12:TmpOut
MV
O
Communication with RTD Unit
Integration of a Serial RTD Unit (Ziehl TR1200)
Connection of the Communication Lines
shows how you connect the RTD box to the SIPROTEC 5 device. Note that Pin 1 of the RJ45 plug is
connected to RTD-B and Pin 2 is connected to RTD-A.
[dwverbau-201112-01.tif, 1, en_US]
Figure 6-60
Connection of the RTD Unit to the SIPROTEC 5 Device
Adding a USART Module
Add a USART-AB-1EL or a USART-AC-2EL USART module in DIGSI to the device. The USART module must be
inserted at one of the plug-in positions for communication modules in the base module or in the CB202
expansion module (refer to the following figure).
[scauser3-190214-01, 1, en_US]
Figure 6-61
Insertion Position for a USART Module
Selecting the SUP Protocol
Select the Slave Unit Protocol (SUP). This protocol is responsible for the communication between the SIPROTEC
5 device and the RTD Unit.
6.5.9
6.5.9.1
Function-Group Types
6.5 Function-Group Type Analog Units
206
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...