Application and Setting Notes
Time Synchronization
In order to ensure the time accuracy of the PMU, you must select IRIG-B as protocol for the GPS clock, see the
following figure. With other settings, the PMU function function group indicates that it is not time synchron-
ized.
[sc_setting time source_2014-09-09, 1, en_US]
Figure 6-30
Setting Time Synchronization
To detect a lack of synchronization quickly, also set the waiting time for the failure indication of the loss of
time synchronization to the smallest possible value, thus to 1 s.
Parameter: Mode
•
Default setting
(_:10621:1) Mode
=
on
Activate and deactivate the PMU or switch to Test mode via the parameter
Mode
. The possible setting values
are
on
,
off
and
test
. In Test mode, the PMU data is marked as invalid.
Parameter: Reporting rate
•
Default setting
(_:10621:102) Reporting rate
=
10 frames/s
With the parameter
Reporting rate
, you specify the number of telegrams that are compiled and sent to
the PDC per second.
i
i
NOTE
Different setting values are shown or hidden, depending on the rated frequency set.
6.4.8
Function-Group Types
6.4 Function-Group Type Phasor Measurement Unit (PMU)
SIPROTEC 5, Fault Recorder, Manual
169
C53000-G5040-C018-5, Edition 11.2017
Содержание SIPROTEC 5
Страница 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Страница 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...